25 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 0.53V (2.23%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.63V (2.63%)
Voltage at Load23.5 VLine Loss: 13.4 W
Max Power & Breaker0.6 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A17.83 V (74.31%)6.2 V29.42 V (122.57%)445.8 WDrop High
2.5 mm²24 A18 A10.7 V (44.58%)13.3 V17.65 V (73.54%)267.5 WDrop High
4 mm²32 A25 A6.69 V (27.86%)17.3 V11.03 V (45.96%)167.2 WDrop High
6 mm²41 A32 A4.46 V (18.58%)19.5 V7.35 V (30.64%)111.5 WDrop High
10 mm²57 A44 A2.67 V (11.15%)21.3 V4.41 V (18.39%)66.9 WDrop High
16 mm²76 A59 A1.67 V (6.97%)22.3 V2.76 V (11.49%)41.8 WDrop High
25 mm²101 A78 A1.07 V (4.46%)22.9 V1.76 V (7.35%)26.7 W~ ≤5%
35 mm²125 A97 A0.76 V (3.18%)23.2 V1.26 V (5.25%)19.1 W~ ≤5%
50 mm²151 A118 A0.53 V (2.23%)23.5 V0.88 V (3.68%)13.4 W✓ OK (≤3%)
70 mm²192 A150 A0.38 V (1.59%)23.6 V0.63 V (2.63%)9.6 W✓ OK (≤3%)
95 mm²232 A181 A0.28 V (1.17%)23.7 V0.46 V (1.94%)7.0 W✓ OK (≤3%)
120 mm²269 A210 A0.22 V (0.93%)23.8 V0.37 V (1.53%)5.6 W✓ OK (≤3%)
150 mm²309 A241 A0.18 V (0.74%)23.8 V0.29 V (1.23%)4.5 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.6%)23.9 V0.24 V (0.99%)3.6 W✓ OK (≤3%)
240 mm²415 A324 A0.11 V (0.46%)23.9 V0.18 V (0.77%)2.8 W✓ OK (≤3%)
300 mm²477 A372 A0.09 V (0.37%)23.9 V0.15 V (0.61%)2.2 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.28%)23.9 V0.11 V (0.46%)1.7 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 25A at 25 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 25A over 25m at 24V (voltage drop: 0.53V or 2.23%).

What is the power capacity of 25A at 24V?

At unity power factor, 25A at 24V supports 0.6 kW with a standard 25A circuit breaker.