16 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 0.68V (2.85%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 0.56V (2.35%)
Voltage at Load23.3 VLine Loss: 11.0 W
Max Power & Breaker0.38 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.41 V (47.56%)12.6 V18.83 V (78.44%)182.6 WDrop High
2.5 mm²24 A18 A6.85 V (28.53%)17.2 V11.3 V (47.07%)109.6 WDrop High
4 mm²32 A25 A4.28 V (17.83%)19.7 V7.06 V (29.42%)68.5 WDrop High
6 mm²41 A32 A2.85 V (11.89%)21.1 V4.71 V (19.61%)45.7 WDrop High
10 mm²57 A44 A1.71 V (7.13%)22.3 V2.82 V (11.77%)27.4 WDrop High
16 mm²76 A59 A1.07 V (4.46%)22.9 V1.76 V (7.35%)17.1 W~ ≤5%
25 mm²101 A78 A0.68 V (2.85%)23.3 V1.13 V (4.71%)11.0 W✓ OK (≤3%)
35 mm²125 A97 A0.49 V (2.04%)23.5 V0.81 V (3.36%)7.8 W✓ OK (≤3%)
50 mm²151 A118 A0.34 V (1.43%)23.7 V0.56 V (2.35%)5.5 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (1.02%)23.8 V0.4 V (1.68%)3.9 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.75%)23.8 V0.3 V (1.24%)2.9 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.59%)23.9 V0.24 V (0.98%)2.3 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.48%)23.9 V0.19 V (0.78%)1.8 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.39%)23.9 V0.15 V (0.64%)1.5 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.3%)23.9 V0.12 V (0.49%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.24%)23.9 V0.09 V (0.39%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.18%)24.0 V0.07 V (0.29%)0.7 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 16A at 25 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 16A over 25m at 24V (voltage drop: 0.68V or 2.85%).

What is the power capacity of 16A at 24V?

At unity power factor, 16A at 24V supports 0.38 kW with a standard 16A circuit breaker.