⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

125 Amp Cable Size at 60 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 7.94V (1.91%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.55V (1.58%)
Voltage at Load407.1 VLine Loss: 1719.6 W
Max Power & Breaker89.85 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A185.33 V (44.66%)229.7 V305.71 V (73.66%)40125.0 WDrop High
2.5 mm²24 A18 A111.2 V (26.79%)303.8 V183.42 V (44.2%)24075.0 WDrop High
4 mm²32 A25 A69.5 V (16.75%)345.5 V114.64 V (27.62%)15046.9 WDrop High
6 mm²41 A32 A46.33 V (11.16%)368.7 V76.43 V (18.42%)10031.2 WDrop High
10 mm²57 A44 A27.8 V (6.7%)387.2 V45.86 V (11.05%)6018.8 WDrop High
16 mm²76 A59 A17.37 V (4.19%)397.6 V28.66 V (6.91%)3761.7 WDrop High
25 mm²101 A78 A11.12 V (2.68%)403.9 V18.34 V (4.42%)2407.5 WDrop High
35 mm²125 A97 A7.94 V (1.91%)407.1 V13.1 V (3.16%)1719.6 W✓ OK (≤3%)
50 mm²151 A118 A5.56 V (1.34%)409.4 V9.17 V (2.21%)1203.8 W✓ OK (≤3%)
70 mm²192 A150 A3.97 V (0.96%)411.0 V6.55 V (1.58%)859.8 W✓ OK (≤3%)
95 mm²232 A181 A2.93 V (0.71%)412.1 V4.83 V (1.16%)633.6 W✓ OK (≤3%)
120 mm²269 A210 A2.32 V (0.56%)412.7 V3.82 V (0.92%)501.6 W✓ OK (≤3%)
150 mm²309 A241 A1.85 V (0.45%)413.1 V3.06 V (0.74%)401.2 W✓ OK (≤3%)
185 mm²353 A275 A1.5 V (0.36%)413.5 V2.48 V (0.6%)325.3 W✓ OK (≤3%)
240 mm²415 A324 A1.16 V (0.28%)413.8 V1.91 V (0.46%)250.8 W✓ OK (≤3%)
300 mm²477 A372 A0.93 V (0.22%)414.1 V1.53 V (0.37%)200.6 W✓ OK (≤3%)
400 mm²570 A445 A0.69 V (0.17%)414.3 V1.15 V (0.28%)150.5 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 60 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 125A at 60 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 60m at 415V (voltage drop: 7.94V or 1.91%).

What is the power capacity of 125A at 415V?

At unity power factor, 125A at 415V supports 89.85 kW with a standard 125A circuit breaker.