125 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 0.66V (0.1%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.55V (0.08%)
Voltage at Load689.3 VLine Loss: 143.3 W
Max Power & Breaker149.39 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A15.44 V (2.24%)674.6 V25.48 V (3.69%)3343.8 WDrop High
2.5 mm²24 A18 A9.27 V (1.34%)680.7 V15.29 V (2.22%)2006.2 WDrop High
4 mm²32 A25 A5.79 V (0.84%)684.2 V9.55 V (1.38%)1253.9 WDrop High
6 mm²41 A32 A3.86 V (0.56%)686.1 V6.37 V (0.92%)835.9 WDrop High
10 mm²57 A44 A2.32 V (0.34%)687.7 V3.82 V (0.55%)501.6 WDrop High
16 mm²76 A59 A1.45 V (0.21%)688.6 V2.39 V (0.35%)313.5 WDrop High
25 mm²101 A78 A0.93 V (0.13%)689.1 V1.53 V (0.22%)200.6 WDrop High
35 mm²125 A97 A0.66 V (0.1%)689.3 V1.09 V (0.16%)143.3 W✓ OK (≤3%)
50 mm²151 A118 A0.46 V (0.07%)689.5 V0.76 V (0.11%)100.3 W✓ OK (≤3%)
70 mm²192 A150 A0.33 V (0.05%)689.7 V0.55 V (0.08%)71.7 W✓ OK (≤3%)
95 mm²232 A181 A0.24 V (0.04%)689.8 V0.4 V (0.06%)52.8 W✓ OK (≤3%)
120 mm²269 A210 A0.19 V (0.03%)689.8 V0.32 V (0.05%)41.8 W✓ OK (≤3%)
150 mm²309 A241 A0.15 V (0.02%)689.8 V0.25 V (0.04%)33.4 W✓ OK (≤3%)
185 mm²353 A275 A0.13 V (0.02%)689.9 V0.21 V (0.03%)27.1 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.01%)689.9 V0.16 V (0.02%)20.9 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.01%)689.9 V0.13 V (0.02%)16.7 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.01%)689.9 V0.1 V (0.01%)12.5 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 125A at 5 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 5m at 690V (voltage drop: 0.66V or 0.1%).

What is the power capacity of 125A at 690V?

At unity power factor, 125A at 690V supports 149.39 kW with a standard 125A circuit breaker.