⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

1000 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.11V (1.96%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 26.75V (6.45%)
Voltage at Load406.9 VLine Loss: 14043.8 W
Max Power & Breaker718.8 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4324.35 V (1042.01%)0.0 V7133.16 V (1718.83%)7490000.0 WDrop High
2.5 mm²24 A18 A2594.61 V (625.21%)0.0 V4279.9 V (1031.3%)4494000.0 WDrop High
4 mm²32 A25 A1621.63 V (390.75%)0.0 V2674.94 V (644.56%)2808750.0 WDrop High
6 mm²41 A32 A1081.09 V (260.5%)0.0 V1783.29 V (429.71%)1872500.0 WDrop High
10 mm²57 A44 A648.65 V (156.3%)0.0 V1069.97 V (257.83%)1123500.0 WDrop High
16 mm²76 A59 A405.41 V (97.69%)9.6 V668.73 V (161.14%)702187.5 WDrop High
25 mm²101 A78 A259.46 V (62.52%)155.5 V427.99 V (103.13%)449400.0 WDrop High
35 mm²125 A97 A185.33 V (44.66%)229.7 V305.71 V (73.66%)321000.0 WDrop High
50 mm²151 A118 A129.73 V (31.26%)285.3 V213.99 V (51.57%)224700.0 WDrop High
70 mm²192 A150 A92.66 V (22.33%)322.3 V152.85 V (36.83%)160500.0 WDrop High
95 mm²232 A181 A68.28 V (16.45%)346.7 V112.63 V (27.14%)118263.2 WDrop High
120 mm²269 A210 A54.05 V (13.03%)360.9 V89.16 V (21.49%)93625.0 WDrop High
150 mm²309 A241 A43.24 V (10.42%)371.8 V71.33 V (17.19%)74900.0 WDrop High
185 mm²353 A275 A35.06 V (8.45%)379.9 V57.84 V (13.94%)60729.7 WDrop High
240 mm²415 A324 A27.03 V (6.51%)388.0 V44.58 V (10.74%)46812.5 WDrop High
300 mm²477 A372 A21.62 V (5.21%)393.4 V35.67 V (8.59%)37450.0 WDrop High
400 mm²570 A445 A16.22 V (3.91%)398.8 V26.75 V (6.45%)28087.5 WDrop High

FAQ — 1000 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 1000A at 175 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 175m at 415V (voltage drop: 8.11V or 1.96%).

What is the power capacity of 1000A at 415V?

At unity power factor, 1000A at 415V supports 718.8 kW with a standard 1000A circuit breaker.