1000 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.11V (1.18%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 26.75V (3.88%)
Voltage at Load681.9 VLine Loss: 14043.8 W
Max Power & Breaker1195.12 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4324.35 V (626.72%)0.0 V7133.16 V (1033.79%)7490000.0 WDrop High
2.5 mm²24 A18 A2594.61 V (376.03%)0.0 V4279.9 V (620.28%)4494000.0 WDrop High
4 mm²32 A25 A1621.63 V (235.02%)0.0 V2674.94 V (387.67%)2808750.0 WDrop High
6 mm²41 A32 A1081.09 V (156.68%)0.0 V1783.29 V (258.45%)1872500.0 WDrop High
10 mm²57 A44 A648.65 V (94.01%)41.3 V1069.97 V (155.07%)1123500.0 WDrop High
16 mm²76 A59 A405.41 V (58.75%)284.6 V668.73 V (96.92%)702187.5 WDrop High
25 mm²101 A78 A259.46 V (37.6%)430.5 V427.99 V (62.03%)449400.0 WDrop High
35 mm²125 A97 A185.33 V (26.86%)504.7 V305.71 V (44.31%)321000.0 WDrop High
50 mm²151 A118 A129.73 V (18.8%)560.3 V213.99 V (31.01%)224700.0 WDrop High
70 mm²192 A150 A92.66 V (13.43%)597.3 V152.85 V (22.15%)160500.0 WDrop High
95 mm²232 A181 A68.28 V (9.9%)621.7 V112.63 V (16.32%)118263.2 WDrop High
120 mm²269 A210 A54.05 V (7.83%)635.9 V89.16 V (12.92%)93625.0 WDrop High
150 mm²309 A241 A43.24 V (6.27%)646.8 V71.33 V (10.34%)74900.0 WDrop High
185 mm²353 A275 A35.06 V (5.08%)654.9 V57.84 V (8.38%)60729.7 WDrop High
240 mm²415 A324 A27.03 V (3.92%)663.0 V44.58 V (6.46%)46812.5 WDrop High
300 mm²477 A372 A21.62 V (3.13%)668.4 V35.67 V (5.17%)37450.0 WDrop High
400 mm²570 A445 A16.22 V (2.35%)673.8 V26.75 V (3.88%)28087.5 WDrop High

FAQ — 1000 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 1000A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 175m at 690V (voltage drop: 8.11V or 1.18%).

What is the power capacity of 1000A at 690V?

At unity power factor, 1000A at 690V supports 1195.12 kW with a standard 1000A circuit breaker.