1000 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 11.59V (1.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 38.21V (5.54%)
Voltage at Load678.4 VLine Loss: 20062.5 W
Max Power & Breaker1195.12 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6177.65 V (895.31%)0.0 V10190.23 V (1476.85%)10700000.0 WDrop High
2.5 mm²24 A18 A3706.59 V (537.19%)0.0 V6114.14 V (886.11%)6420000.0 WDrop High
4 mm²32 A25 A2316.62 V (335.74%)0.0 V3821.34 V (553.82%)4012500.0 WDrop High
6 mm²41 A32 A1544.41 V (223.83%)0.0 V2547.56 V (369.21%)2675000.0 WDrop High
10 mm²57 A44 A926.65 V (134.3%)0.0 V1528.53 V (221.53%)1605000.0 WDrop High
16 mm²76 A59 A579.15 V (83.94%)110.8 V955.33 V (138.45%)1003125.0 WDrop High
25 mm²101 A78 A370.66 V (53.72%)319.3 V611.41 V (88.61%)642000.0 WDrop High
35 mm²125 A97 A264.76 V (38.37%)425.2 V436.72 V (63.29%)458571.4 WDrop High
50 mm²151 A118 A185.33 V (26.86%)504.7 V305.71 V (44.31%)321000.0 WDrop High
70 mm²192 A150 A132.38 V (19.19%)557.6 V218.36 V (31.65%)229285.7 WDrop High
95 mm²232 A181 A97.54 V (14.14%)592.5 V160.9 V (23.32%)168947.4 WDrop High
120 mm²269 A210 A77.22 V (11.19%)612.8 V127.38 V (18.46%)133750.0 WDrop High
150 mm²309 A241 A61.78 V (8.95%)628.2 V101.9 V (14.77%)107000.0 WDrop High
185 mm²353 A275 A50.09 V (7.26%)639.9 V82.62 V (11.97%)86756.8 WDrop High
240 mm²415 A324 A38.61 V (5.6%)651.4 V63.69 V (9.23%)66875.0 WDrop High
300 mm²477 A372 A30.89 V (4.48%)659.1 V50.95 V (7.38%)53500.0 WDrop High
400 mm²570 A445 A23.17 V (3.36%)666.8 V38.21 V (5.54%)40125.0 WDrop High

FAQ — 1000 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 1000A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 1000A over 250m at 690V (voltage drop: 11.59V or 1.68%).

What is the power capacity of 1000A at 690V?

At unity power factor, 1000A at 690V supports 1195.12 kW with a standard 1000A circuit breaker.