⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

1000 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 15.44V (2.24%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 76.43V (11.08%)
Voltage at Load674.6 VLine Loss: 26750.0 W
Max Power & Breaker1195.12 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12355.3 V (1790.62%)0.0 V20380.46 V (2953.69%)21400000.0 WDrop High
2.5 mm²24 A18 A7413.18 V (1074.37%)0.0 V12228.28 V (1772.21%)12840000.0 WDrop High
4 mm²32 A25 A4633.24 V (671.48%)0.0 V7642.67 V (1107.63%)8025000.0 WDrop High
6 mm²41 A32 A3088.82 V (447.66%)0.0 V5095.12 V (738.42%)5350000.0 WDrop High
10 mm²57 A44 A1853.29 V (268.59%)0.0 V3057.07 V (443.05%)3210000.0 WDrop High
16 mm²76 A59 A1158.31 V (167.87%)0.0 V1910.67 V (276.91%)2006250.0 WDrop High
25 mm²101 A78 A741.32 V (107.44%)0.0 V1222.83 V (177.22%)1284000.0 WDrop High
35 mm²125 A97 A529.51 V (76.74%)160.5 V873.45 V (126.59%)917142.9 WDrop High
50 mm²151 A118 A370.66 V (53.72%)319.3 V611.41 V (88.61%)642000.0 WDrop High
70 mm²192 A150 A264.76 V (38.37%)425.2 V436.72 V (63.29%)458571.4 WDrop High
95 mm²232 A181 A195.08 V (28.27%)494.9 V321.8 V (46.64%)337894.7 WDrop High
120 mm²269 A210 A154.44 V (22.38%)535.6 V254.76 V (36.92%)267500.0 WDrop High
150 mm²309 A241 A123.55 V (17.91%)566.4 V203.8 V (29.54%)214000.0 WDrop High
185 mm²353 A275 A100.18 V (14.52%)589.8 V165.25 V (23.95%)173513.5 WDrop High
240 mm²415 A324 A77.22 V (11.19%)612.8 V127.38 V (18.46%)133750.0 WDrop High
300 mm²477 A372 A61.78 V (8.95%)628.2 V101.9 V (14.77%)107000.0 WDrop High
400 mm²570 A445 A46.33 V (6.71%)643.7 V76.43 V (11.08%)80250.0 WDrop High

FAQ — 1000 Amp Cable Size at 500 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 1000A at 500 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 1000A over 500m at 690V (voltage drop: 15.44V or 2.24%).

What is the power capacity of 1000A at 690V?

At unity power factor, 1000A at 690V supports 1195.12 kW with a standard 1000A circuit breaker.