⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

1000 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 1000 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 11.12V (2.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 91.71V (22.1%)
Voltage at Load403.9 VLine Loss: 19260.0 W
Max Power & Breaker718.8 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14826.35 V (3572.62%)0.0 V24456.56 V (5893.15%)25680000.0 WDrop High
2.5 mm²24 A18 A8895.81 V (2143.57%)0.0 V14673.93 V (3535.89%)15408000.0 WDrop High
4 mm²32 A25 A5559.88 V (1339.73%)0.0 V9171.21 V (2209.93%)9630000.0 WDrop High
6 mm²41 A32 A3706.59 V (893.15%)0.0 V6114.14 V (1473.29%)6420000.0 WDrop High
10 mm²57 A44 A2223.95 V (535.89%)0.0 V3668.48 V (883.97%)3852000.0 WDrop High
16 mm²76 A59 A1389.97 V (334.93%)0.0 V2292.8 V (552.48%)2407500.0 WDrop High
25 mm²101 A78 A889.58 V (214.36%)0.0 V1467.39 V (353.59%)1540800.0 WDrop High
35 mm²125 A97 A635.42 V (153.11%)0.0 V1048.14 V (252.56%)1100571.4 WDrop High
50 mm²151 A118 A444.79 V (107.18%)0.0 V733.7 V (176.79%)770400.0 WDrop High
70 mm²192 A150 A317.71 V (76.56%)97.3 V524.07 V (126.28%)550285.7 WDrop High
95 mm²232 A181 A234.1 V (56.41%)180.9 V386.16 V (93.05%)405473.7 WDrop High
120 mm²269 A210 A185.33 V (44.66%)229.7 V305.71 V (73.66%)321000.0 WDrop High
150 mm²309 A241 A148.26 V (35.73%)266.7 V244.57 V (58.93%)256800.0 WDrop High
185 mm²353 A275 A120.21 V (28.97%)294.8 V198.3 V (47.78%)208216.2 WDrop High
240 mm²415 A324 A92.66 V (22.33%)322.3 V152.85 V (36.83%)160500.0 WDrop High
300 mm²477 A372 A74.13 V (17.86%)340.9 V122.28 V (29.47%)128400.0 WDrop High
400 mm²570 A445 A55.6 V (13.4%)359.4 V91.71 V (22.1%)96300.0 WDrop High

FAQ — 1000 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 1000A at 600 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 1000A over 600m at 415V (voltage drop: 11.12V or 2.68%).

What is the power capacity of 1000A at 415V?

At unity power factor, 1000A at 415V supports 718.8 kW with a standard 1000A circuit breaker.