⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

110 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 110 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.26V (2.62%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.55V (3.24%)
Voltage at Load46.7 VLine Loss: 138.1 W
Max Power & Breaker5.28 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A251.09 V (523.11%)0.0 V414.19 V (862.89%)27620.3 WDrop High
2.5 mm²24 A18 A150.66 V (313.87%)0.0 V248.51 V (517.73%)16572.2 WDrop High
4 mm²32 A25 A94.16 V (196.17%)0.0 V155.32 V (323.58%)10357.6 WDrop High
6 mm²41 A32 A62.77 V (130.78%)0.0 V103.55 V (215.72%)6905.1 WDrop High
10 mm²57 A44 A37.66 V (78.47%)10.3 V62.13 V (129.43%)4143.0 WDrop High
16 mm²76 A59 A23.54 V (49.04%)24.5 V38.83 V (80.9%)2589.4 WDrop High
25 mm²101 A78 A15.07 V (31.39%)32.9 V24.85 V (51.77%)1657.2 WDrop High
35 mm²125 A97 A10.76 V (22.42%)37.2 V17.75 V (36.98%)1183.7 WDrop High
50 mm²151 A118 A7.53 V (15.69%)40.5 V12.43 V (25.89%)828.6 WDrop High
70 mm²192 A150 A5.38 V (11.21%)42.6 V8.88 V (18.49%)591.9 WDrop High
95 mm²232 A181 A3.96 V (8.26%)44.0 V6.54 V (13.62%)436.1 WDrop High
120 mm²269 A210 A3.14 V (6.54%)44.9 V5.18 V (10.79%)345.3 WDrop High
150 mm²309 A241 A2.51 V (5.23%)45.5 V4.14 V (8.63%)276.2 WDrop High
185 mm²353 A275 A2.04 V (4.24%)46.0 V3.36 V (7.0%)223.9 W~ ≤5%
240 mm²415 A324 A1.57 V (3.27%)46.4 V2.59 V (5.39%)172.6 W~ ≤5%
300 mm²477 A372 A1.26 V (2.62%)46.7 V2.07 V (4.31%)138.1 W✓ OK (≤3%)
400 mm²570 A445 A0.94 V (1.96%)47.1 V1.55 V (3.24%)103.6 W✓ OK (≤3%)

FAQ — 110 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 110A at 80 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 110A over 80m at 48V (voltage drop: 1.26V or 2.62%).

What is the power capacity of 110A at 48V?

At unity power factor, 110A at 48V supports 5.28 kW with a standard 110A circuit breaker.