⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

125 Amp Cable Size at 90 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 11.91V (2.87%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 9.83V (2.37%)
Voltage at Load403.1 VLine Loss: 2579.5 W
Max Power & Breaker89.85 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A277.99 V (66.99%)137.0 V458.56 V (110.5%)60187.5 WDrop High
2.5 mm²24 A18 A166.8 V (40.19%)248.2 V275.14 V (66.3%)36112.5 WDrop High
4 mm²32 A25 A104.25 V (25.12%)310.8 V171.96 V (41.44%)22570.3 WDrop High
6 mm²41 A32 A69.5 V (16.75%)345.5 V114.64 V (27.62%)15046.9 WDrop High
10 mm²57 A44 A41.7 V (10.05%)373.3 V68.78 V (16.57%)9028.1 WDrop High
16 mm²76 A59 A26.06 V (6.28%)388.9 V42.99 V (10.36%)5642.6 WDrop High
25 mm²101 A78 A16.68 V (4.02%)398.3 V27.51 V (6.63%)3611.2 WDrop High
35 mm²125 A97 A11.91 V (2.87%)403.1 V19.65 V (4.74%)2579.5 W✓ OK (≤3%)
50 mm²151 A118 A8.34 V (2.01%)406.7 V13.76 V (3.31%)1805.6 W✓ OK (≤3%)
70 mm²192 A150 A5.96 V (1.44%)409.0 V9.83 V (2.37%)1289.7 W✓ OK (≤3%)
95 mm²232 A181 A4.39 V (1.06%)410.6 V7.24 V (1.74%)950.3 W✓ OK (≤3%)
120 mm²269 A210 A3.47 V (0.84%)411.5 V5.73 V (1.38%)752.3 W✓ OK (≤3%)
150 mm²309 A241 A2.78 V (0.67%)412.2 V4.59 V (1.1%)601.9 W✓ OK (≤3%)
185 mm²353 A275 A2.25 V (0.54%)412.7 V3.72 V (0.9%)488.0 W✓ OK (≤3%)
240 mm²415 A324 A1.74 V (0.42%)413.3 V2.87 V (0.69%)376.2 W✓ OK (≤3%)
300 mm²477 A372 A1.39 V (0.33%)413.6 V2.29 V (0.55%)300.9 W✓ OK (≤3%)
400 mm²570 A445 A1.04 V (0.25%)414.0 V1.72 V (0.41%)225.7 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 90 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 125A at 90 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 90m at 415V (voltage drop: 11.91V or 2.87%).

What is the power capacity of 125A at 415V?

At unity power factor, 125A at 415V supports 89.85 kW with a standard 125A circuit breaker.