125 Amp Cable Size at 90 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 1.2V (2.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.99V (4.14%)
Voltage at Load46.8 VLine Loss: 150.5 W
Max Power & Breaker6.0 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A321.0 V (668.75%)0.0 V529.5 V (1103.12%)40125.0 WDrop High
2.5 mm²24 A18 A192.6 V (401.25%)0.0 V317.7 V (661.88%)24075.0 WDrop High
4 mm²32 A25 A120.38 V (250.78%)0.0 V198.56 V (413.67%)15046.9 WDrop High
6 mm²41 A32 A80.25 V (167.19%)0.0 V132.38 V (275.78%)10031.2 WDrop High
10 mm²57 A44 A48.15 V (100.31%)0.0 V79.42 V (165.47%)6018.8 WDrop High
16 mm²76 A59 A30.09 V (62.7%)17.9 V49.64 V (103.42%)3761.7 WDrop High
25 mm²101 A78 A19.26 V (40.12%)28.7 V31.77 V (66.19%)2407.5 WDrop High
35 mm²125 A97 A13.76 V (28.66%)34.2 V22.69 V (47.28%)1719.6 WDrop High
50 mm²151 A118 A9.63 V (20.06%)38.4 V15.88 V (33.09%)1203.8 WDrop High
70 mm²192 A150 A6.88 V (14.33%)41.1 V11.35 V (23.64%)859.8 WDrop High
95 mm²232 A181 A5.07 V (10.56%)42.9 V8.36 V (17.42%)633.6 WDrop High
120 mm²269 A210 A4.01 V (8.36%)44.0 V6.62 V (13.79%)501.6 WDrop High
150 mm²309 A241 A3.21 V (6.69%)44.8 V5.29 V (11.03%)401.2 WDrop High
185 mm²353 A275 A2.6 V (5.42%)45.4 V4.29 V (8.94%)325.3 WDrop High
240 mm²415 A324 A2.01 V (4.18%)46.0 V3.31 V (6.89%)250.8 W~ ≤5%
300 mm²477 A372 A1.6 V (3.34%)46.4 V2.65 V (5.52%)200.6 W~ ≤5%
400 mm²570 A445 A1.2 V (2.51%)46.8 V1.99 V (4.14%)150.5 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 90 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 125A at 90 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 125A over 90m at 48V (voltage drop: 1.2V or 2.51%).

What is the power capacity of 125A at 48V?

At unity power factor, 125A at 48V supports 6.0 kW with a standard 125A circuit breaker.