15 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 1.18V (2.46%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 1.24V (2.57%)
Voltage at Load46.8 VLine Loss: 17.7 W
Max Power & Breaker0.72 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A74.9 V (156.04%)0.0 V123.55 V (257.4%)1123.5 WDrop High
2.5 mm²24 A18 A44.94 V (93.62%)3.1 V74.13 V (154.44%)674.1 WDrop High
4 mm²32 A25 A28.09 V (58.52%)19.9 V46.33 V (96.52%)421.3 WDrop High
6 mm²41 A32 A18.72 V (39.01%)29.3 V30.89 V (64.35%)280.9 WDrop High
10 mm²57 A44 A11.23 V (23.41%)36.8 V18.53 V (38.61%)168.5 WDrop High
16 mm²76 A59 A7.02 V (14.63%)41.0 V11.58 V (24.13%)105.3 WDrop High
25 mm²101 A78 A4.49 V (9.36%)43.5 V7.41 V (15.44%)67.4 WDrop High
35 mm²125 A97 A3.21 V (6.69%)44.8 V5.29 V (11.03%)48.1 WDrop High
50 mm²151 A118 A2.25 V (4.68%)45.8 V3.71 V (7.72%)33.7 W~ ≤5%
70 mm²192 A150 A1.6 V (3.34%)46.4 V2.65 V (5.52%)24.1 W~ ≤5%
95 mm²232 A181 A1.18 V (2.46%)46.8 V1.95 V (4.06%)17.7 W✓ OK (≤3%)
120 mm²269 A210 A0.94 V (1.95%)47.1 V1.54 V (3.22%)14.0 W✓ OK (≤3%)
150 mm²309 A241 A0.75 V (1.56%)47.3 V1.24 V (2.57%)11.2 W✓ OK (≤3%)
185 mm²353 A275 A0.61 V (1.27%)47.4 V1.0 V (2.09%)9.1 W✓ OK (≤3%)
240 mm²415 A324 A0.47 V (0.98%)47.5 V0.77 V (1.61%)7.0 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (0.78%)47.6 V0.62 V (1.29%)5.6 W✓ OK (≤3%)
400 mm²570 A445 A0.28 V (0.59%)47.7 V0.46 V (0.97%)4.2 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 175 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 15A at 175 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 15A over 175m at 48V (voltage drop: 1.18V or 2.46%).

What is the power capacity of 15A at 48V?

At unity power factor, 15A at 48V supports 0.72 kW with a standard 15A circuit breaker.