15 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 5 m (16.4 ft).
Copper Cable (≤3% Drop)1.5 mm²Drop: 1.85V (0.45%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 1.83V (0.44%)
Voltage at Load413.1 VLine Loss: 48.1 W
Max Power & Breaker10.78 kW15A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1.85 V (0.45%) | 413.1 V | 3.06 V (0.74%) | 48.1 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 1.11 V (0.27%) | 413.9 V | 1.83 V (0.44%) | 28.9 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 0.69 V (0.17%) | 414.3 V | 1.15 V (0.28%) | 18.1 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 0.46 V (0.11%) | 414.5 V | 0.76 V (0.18%) | 12.0 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 0.28 V (0.07%) | 414.7 V | 0.46 V (0.11%) | 7.2 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.17 V (0.04%) | 414.8 V | 0.29 V (0.07%) | 4.5 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.11 V (0.03%) | 414.9 V | 0.18 V (0.04%) | 2.9 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.08 V (0.02%) | 414.9 V | 0.13 V (0.03%) | 2.1 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.06 V (0.01%) | 414.9 V | 0.09 V (0.02%) | 1.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.04 V (0.01%) | 415.0 V | 0.07 V (0.02%) | 1.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.03 V (0.01%) | 415.0 V | 0.05 V (0.01%) | 0.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.02 V (0.01%) | 415.0 V | 0.04 V (0.01%) | 0.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.02 V (0.0%) | 415.0 V | 0.03 V (0.01%) | 0.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.02 V (0.0%) | 415.0 V | 0.02 V (0.01%) | 0.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.01 V (0.0%) | 415.0 V | 0.02 V (0.0%) | 0.3 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.01 V (0.0%) | 415.0 V | 0.02 V (0.0%) | 0.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.01 V (0.0%) | 415.0 V | 0.01 V (0.0%) | 0.2 W | ✓ OK (≤3%) |
FAQ — 15 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 15A at 5 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 15A over 5m at 415V (voltage drop: 1.85V or 0.45%).
What is the power capacity of 15A at 415V?
At unity power factor, 15A at 415V supports 10.78 kW with a standard 15A circuit breaker.
Related Lengths & Currents (415V)
15A · 10m (415V)15A · 15m (415V)15A · 20m (415V)15A · 25m (415V)15A · 30m (415V)15A · 35m (415V)15A · 40m (415V)15A · 45m (415V)15A · 50m (415V)15A · 60m (415V)15A · 70m (415V)10A · 5m (415V)16A · 5m (415V)20A · 5m (415V)25A · 5m (415V)32A · 5m (415V)40A · 5m (415V)50A · 5m (415V)63A · 5m (415V)80A · 5m (415V)100A · 5m (415V)125A · 5m (415V)160A · 5m (415V)200A · 5m (415V)