15 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 10.01V (2.41%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 10.32V (2.49%)
Voltage at Load405.0 VLine Loss: 260.0 W
Max Power & Breaker10.78 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A16.68 V (4.02%)398.3 V27.51 V (6.63%)433.4 W~ ≤5%
2.5 mm²24 A18 A10.01 V (2.41%)405.0 V16.51 V (3.98%)260.0 W✓ OK (≤3%)
4 mm²32 A25 A6.25 V (1.51%)408.7 V10.32 V (2.49%)162.5 W✓ OK (≤3%)
6 mm²41 A32 A4.17 V (1.0%)410.8 V6.88 V (1.66%)108.3 W✓ OK (≤3%)
10 mm²57 A44 A2.5 V (0.6%)412.5 V4.13 V (0.99%)65.0 W✓ OK (≤3%)
16 mm²76 A59 A1.56 V (0.38%)413.4 V2.58 V (0.62%)40.6 W✓ OK (≤3%)
25 mm²101 A78 A1.0 V (0.24%)414.0 V1.65 V (0.4%)26.0 W✓ OK (≤3%)
35 mm²125 A97 A0.71 V (0.17%)414.3 V1.18 V (0.28%)18.6 W✓ OK (≤3%)
50 mm²151 A118 A0.5 V (0.12%)414.5 V0.83 V (0.2%)13.0 W✓ OK (≤3%)
70 mm²192 A150 A0.36 V (0.09%)414.6 V0.59 V (0.14%)9.3 W✓ OK (≤3%)
95 mm²232 A181 A0.26 V (0.06%)414.7 V0.43 V (0.1%)6.8 W✓ OK (≤3%)
120 mm²269 A210 A0.21 V (0.05%)414.8 V0.34 V (0.08%)5.4 W✓ OK (≤3%)
150 mm²309 A241 A0.17 V (0.04%)414.8 V0.28 V (0.07%)4.3 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.03%)414.9 V0.22 V (0.05%)3.5 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.03%)414.9 V0.17 V (0.04%)2.7 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.02%)414.9 V0.14 V (0.03%)2.2 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.02%)414.9 V0.1 V (0.02%)1.6 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 15A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 15A over 45m at 415V (voltage drop: 10.01V or 2.41%).

What is the power capacity of 15A at 415V?

At unity power factor, 15A at 415V supports 10.78 kW with a standard 15A circuit breaker.