⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

15 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 5.56V (1.34%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 5.5V (1.33%)
Voltage at Load409.4 VLine Loss: 144.4 W
Max Power & Breaker10.78 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5.56 V (1.34%)409.4 V9.17 V (2.21%)144.4 W✓ OK (≤3%)
2.5 mm²24 A18 A3.34 V (0.8%)411.7 V5.5 V (1.33%)86.7 W✓ OK (≤3%)
4 mm²32 A25 A2.08 V (0.5%)412.9 V3.44 V (0.83%)54.2 W✓ OK (≤3%)
6 mm²41 A32 A1.39 V (0.33%)413.6 V2.29 V (0.55%)36.1 W✓ OK (≤3%)
10 mm²57 A44 A0.83 V (0.2%)414.2 V1.38 V (0.33%)21.7 W✓ OK (≤3%)
16 mm²76 A59 A0.52 V (0.13%)414.5 V0.86 V (0.21%)13.5 W✓ OK (≤3%)
25 mm²101 A78 A0.33 V (0.08%)414.7 V0.55 V (0.13%)8.7 W✓ OK (≤3%)
35 mm²125 A97 A0.24 V (0.06%)414.8 V0.39 V (0.09%)6.2 W✓ OK (≤3%)
50 mm²151 A118 A0.17 V (0.04%)414.8 V0.28 V (0.07%)4.3 W✓ OK (≤3%)
70 mm²192 A150 A0.12 V (0.03%)414.9 V0.2 V (0.05%)3.1 W✓ OK (≤3%)
95 mm²232 A181 A0.09 V (0.02%)414.9 V0.14 V (0.03%)2.3 W✓ OK (≤3%)
120 mm²269 A210 A0.07 V (0.02%)414.9 V0.11 V (0.03%)1.8 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.01%)414.9 V0.09 V (0.02%)1.4 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.01%)415.0 V0.07 V (0.02%)1.2 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.01%)415.0 V0.06 V (0.01%)0.9 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.01%)415.0 V0.05 V (0.01%)0.7 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)415.0 V0.03 V (0.01%)0.5 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 15A at 15 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 15A over 15m at 415V (voltage drop: 5.56V or 1.34%).

What is the power capacity of 15A at 415V?

At unity power factor, 15A at 415V supports 10.78 kW with a standard 15A circuit breaker.