15 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 9.17V (2.21%)
Voltage at Load405.7 VLine Loss: 240.7 W
Max Power & Breaker10.78 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.27 V (2.23%)405.7 V15.29 V (3.68%)240.7 W✓ OK (≤3%)
2.5 mm²24 A18 A5.56 V (1.34%)409.4 V9.17 V (2.21%)144.4 W✓ OK (≤3%)
4 mm²32 A25 A3.47 V (0.84%)411.5 V5.73 V (1.38%)90.3 W✓ OK (≤3%)
6 mm²41 A32 A2.32 V (0.56%)412.7 V3.82 V (0.92%)60.2 W✓ OK (≤3%)
10 mm²57 A44 A1.39 V (0.33%)413.6 V2.29 V (0.55%)36.1 W✓ OK (≤3%)
16 mm²76 A59 A0.87 V (0.21%)414.1 V1.43 V (0.35%)22.6 W✓ OK (≤3%)
25 mm²101 A78 A0.56 V (0.13%)414.4 V0.92 V (0.22%)14.4 W✓ OK (≤3%)
35 mm²125 A97 A0.4 V (0.1%)414.6 V0.66 V (0.16%)10.3 W✓ OK (≤3%)
50 mm²151 A118 A0.28 V (0.07%)414.7 V0.46 V (0.11%)7.2 W✓ OK (≤3%)
70 mm²192 A150 A0.2 V (0.05%)414.8 V0.33 V (0.08%)5.2 W✓ OK (≤3%)
95 mm²232 A181 A0.15 V (0.04%)414.9 V0.24 V (0.06%)3.8 W✓ OK (≤3%)
120 mm²269 A210 A0.12 V (0.03%)414.9 V0.19 V (0.05%)3.0 W✓ OK (≤3%)
150 mm²309 A241 A0.09 V (0.02%)414.9 V0.15 V (0.04%)2.4 W✓ OK (≤3%)
185 mm²353 A275 A0.08 V (0.02%)414.9 V0.12 V (0.03%)2.0 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.01%)414.9 V0.1 V (0.02%)1.5 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.01%)415.0 V0.08 V (0.02%)1.2 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)415.0 V0.06 V (0.01%)0.9 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 15A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 15A over 25m at 415V (voltage drop: 9.27V or 2.23%).

What is the power capacity of 15A at 415V?

At unity power factor, 15A at 415V supports 10.78 kW with a standard 15A circuit breaker.