15 Amp Cable Size at 500 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 1.34V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.32V (2.76%)
Voltage at Load46.7 VLine Loss: 20.1 W
Max Power & Breaker0.72 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A214.0 V (445.83%)0.0 V353.0 V (735.42%)3210.0 WDrop High
2.5 mm²24 A18 A128.4 V (267.5%)0.0 V211.8 V (441.25%)1926.0 WDrop High
4 mm²32 A25 A80.25 V (167.19%)0.0 V132.38 V (275.78%)1203.8 WDrop High
6 mm²41 A32 A53.5 V (111.46%)0.0 V88.25 V (183.85%)802.5 WDrop High
10 mm²57 A44 A32.1 V (66.87%)15.9 V52.95 V (110.31%)481.5 WDrop High
16 mm²76 A59 A20.06 V (41.8%)27.9 V33.09 V (68.95%)300.9 WDrop High
25 mm²101 A78 A12.84 V (26.75%)35.2 V21.18 V (44.12%)192.6 WDrop High
35 mm²125 A97 A9.17 V (19.11%)38.8 V15.13 V (31.52%)137.6 WDrop High
50 mm²151 A118 A6.42 V (13.38%)41.6 V10.59 V (22.06%)96.3 WDrop High
70 mm²192 A150 A4.59 V (9.55%)43.4 V7.56 V (15.76%)68.8 WDrop High
95 mm²232 A181 A3.38 V (7.04%)44.6 V5.57 V (11.61%)50.7 WDrop High
120 mm²269 A210 A2.67 V (5.57%)45.3 V4.41 V (9.19%)40.1 WDrop High
150 mm²309 A241 A2.14 V (4.46%)45.9 V3.53 V (7.35%)32.1 W~ ≤5%
185 mm²353 A275 A1.74 V (3.61%)46.3 V2.86 V (5.96%)26.0 W~ ≤5%
240 mm²415 A324 A1.34 V (2.79%)46.7 V2.21 V (4.6%)20.1 W✓ OK (≤3%)
300 mm²477 A372 A1.07 V (2.23%)46.9 V1.76 V (3.68%)16.1 W✓ OK (≤3%)
400 mm²570 A445 A0.8 V (1.67%)47.2 V1.32 V (2.76%)12.0 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 500 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 15A at 500 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 15A over 500m at 48V (voltage drop: 1.34V or 2.79%).

What is the power capacity of 15A at 48V?

At unity power factor, 15A at 48V supports 0.72 kW with a standard 15A circuit breaker.