16 Amp Cable Size at 20 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 0.55V (2.28%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 0.65V (2.69%)
Voltage at Load23.5 VLine Loss: 8.8 W
Max Power & Breaker0.38 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.13 V (38.04%)14.9 V15.06 V (62.76%)146.1 WDrop High
2.5 mm²24 A18 A5.48 V (22.83%)18.5 V9.04 V (37.65%)87.7 WDrop High
4 mm²32 A25 A3.42 V (14.27%)20.6 V5.65 V (23.53%)54.8 WDrop High
6 mm²41 A32 A2.28 V (9.51%)21.7 V3.77 V (15.69%)36.5 WDrop High
10 mm²57 A44 A1.37 V (5.71%)22.6 V2.26 V (9.41%)21.9 WDrop High
16 mm²76 A59 A0.86 V (3.57%)23.1 V1.41 V (5.88%)13.7 W~ ≤5%
25 mm²101 A78 A0.55 V (2.28%)23.5 V0.9 V (3.77%)8.8 W✓ OK (≤3%)
35 mm²125 A97 A0.39 V (1.63%)23.6 V0.65 V (2.69%)6.3 W✓ OK (≤3%)
50 mm²151 A118 A0.27 V (1.14%)23.7 V0.45 V (1.88%)4.4 W✓ OK (≤3%)
70 mm²192 A150 A0.2 V (0.82%)23.8 V0.32 V (1.34%)3.1 W✓ OK (≤3%)
95 mm²232 A181 A0.14 V (0.6%)23.9 V0.24 V (0.99%)2.3 W✓ OK (≤3%)
120 mm²269 A210 A0.11 V (0.48%)23.9 V0.19 V (0.78%)1.8 W✓ OK (≤3%)
150 mm²309 A241 A0.09 V (0.38%)23.9 V0.15 V (0.63%)1.5 W✓ OK (≤3%)
185 mm²353 A275 A0.07 V (0.31%)23.9 V0.12 V (0.51%)1.2 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.24%)23.9 V0.09 V (0.39%)0.9 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.19%)24.0 V0.08 V (0.31%)0.7 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.14%)24.0 V0.06 V (0.24%)0.5 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 20 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 16A at 20 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 16A over 20m at 24V (voltage drop: 0.55V or 2.28%).

What is the power capacity of 16A at 24V?

At unity power factor, 16A at 24V supports 0.38 kW with a standard 16A circuit breaker.