⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

16 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 0.68V (2.85%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 0.71V (2.94%)
Voltage at Load23.3 VLine Loss: 11.0 W
Max Power & Breaker0.38 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.57 V (19.02%)19.4 V7.53 V (31.38%)73.0 WDrop High
2.5 mm²24 A18 A2.74 V (11.41%)21.3 V4.52 V (18.83%)43.8 WDrop High
4 mm²32 A25 A1.71 V (7.13%)22.3 V2.82 V (11.77%)27.4 WDrop High
6 mm²41 A32 A1.14 V (4.76%)22.9 V1.88 V (7.84%)18.3 W~ ≤5%
10 mm²57 A44 A0.68 V (2.85%)23.3 V1.13 V (4.71%)11.0 W✓ OK (≤3%)
16 mm²76 A59 A0.43 V (1.78%)23.6 V0.71 V (2.94%)6.8 W✓ OK (≤3%)
25 mm²101 A78 A0.27 V (1.14%)23.7 V0.45 V (1.88%)4.4 W✓ OK (≤3%)
35 mm²125 A97 A0.2 V (0.82%)23.8 V0.32 V (1.34%)3.1 W✓ OK (≤3%)
50 mm²151 A118 A0.14 V (0.57%)23.9 V0.23 V (0.94%)2.2 W✓ OK (≤3%)
70 mm²192 A150 A0.1 V (0.41%)23.9 V0.16 V (0.67%)1.6 W✓ OK (≤3%)
95 mm²232 A181 A0.07 V (0.3%)23.9 V0.12 V (0.5%)1.2 W✓ OK (≤3%)
120 mm²269 A210 A0.06 V (0.24%)23.9 V0.09 V (0.39%)0.9 W✓ OK (≤3%)
150 mm²309 A241 A0.05 V (0.19%)24.0 V0.08 V (0.31%)0.7 W✓ OK (≤3%)
185 mm²353 A275 A0.04 V (0.15%)24.0 V0.06 V (0.25%)0.6 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.12%)24.0 V0.05 V (0.2%)0.5 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.1%)24.0 V0.04 V (0.16%)0.4 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.07%)24.0 V0.03 V (0.12%)0.3 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 16A at 10 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 16A over 10m at 24V (voltage drop: 0.68V or 2.85%).

What is the power capacity of 16A at 24V?

At unity power factor, 16A at 24V supports 0.38 kW with a standard 16A circuit breaker.