⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

175 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 175 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.94V (1.95%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.09V (6.43%)
Voltage at Load47.1 VLine Loss: 163.8 W
Max Power & Breaker8.4 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A499.33 V (1040.28%)0.0 V823.67 V (1715.97%)87383.3 WDrop High
2.5 mm²24 A18 A299.6 V (624.17%)0.0 V494.2 V (1029.58%)52430.0 WDrop High
4 mm²32 A25 A187.25 V (390.1%)0.0 V308.88 V (643.49%)32768.7 WDrop High
6 mm²41 A32 A124.83 V (260.07%)0.0 V205.92 V (428.99%)21845.8 WDrop High
10 mm²57 A44 A74.9 V (156.04%)0.0 V123.55 V (257.4%)13107.5 WDrop High
16 mm²76 A59 A46.81 V (97.53%)1.2 V77.22 V (160.87%)8192.2 WDrop High
25 mm²101 A78 A29.96 V (62.42%)18.0 V49.42 V (102.96%)5243.0 WDrop High
35 mm²125 A97 A21.4 V (44.58%)26.6 V35.3 V (73.54%)3745.0 WDrop High
50 mm²151 A118 A14.98 V (31.21%)33.0 V24.71 V (51.48%)2621.5 WDrop High
70 mm²192 A150 A10.7 V (22.29%)37.3 V17.65 V (36.77%)1872.5 WDrop High
95 mm²232 A181 A7.88 V (16.43%)40.1 V13.01 V (27.09%)1379.7 WDrop High
120 mm²269 A210 A6.24 V (13.0%)41.8 V10.3 V (21.45%)1092.3 WDrop High
150 mm²309 A241 A4.99 V (10.4%)43.0 V8.24 V (17.16%)873.8 WDrop High
185 mm²353 A275 A4.05 V (8.43%)44.0 V6.68 V (13.91%)708.5 WDrop High
240 mm²415 A324 A3.12 V (6.5%)44.9 V5.15 V (10.72%)546.1 WDrop High
300 mm²477 A372 A2.5 V (5.2%)45.5 V4.12 V (8.58%)436.9 WDrop High
400 mm²570 A445 A1.87 V (3.9%)46.1 V3.09 V (6.43%)327.7 W~ ≤5%

FAQ — 175 Amp Cable Size at 100 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 175A at 100 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 175A over 100m at 48V (voltage drop: 0.94V or 1.95%).

What is the power capacity of 175A at 48V?

At unity power factor, 175A at 48V supports 8.4 kW with a standard 175A circuit breaker.