20 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 11.86V (1.72%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 12.23V (1.77%)
Voltage at Load678.1 VLine Loss: 410.9 W
Max Power & Breaker23.9 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A19.77 V (2.86%)670.2 V32.61 V (4.73%)684.8 WDrop High
2.5 mm²24 A18 A11.86 V (1.72%)678.1 V19.57 V (2.84%)410.9 W✓ OK (≤3%)
4 mm²32 A25 A7.41 V (1.07%)682.6 V12.23 V (1.77%)256.8 W✓ OK (≤3%)
6 mm²41 A32 A4.94 V (0.72%)685.1 V8.15 V (1.18%)171.2 W✓ OK (≤3%)
10 mm²57 A44 A2.97 V (0.43%)687.0 V4.89 V (0.71%)102.7 W✓ OK (≤3%)
16 mm²76 A59 A1.85 V (0.27%)688.1 V3.06 V (0.44%)64.2 W✓ OK (≤3%)
25 mm²101 A78 A1.19 V (0.17%)688.8 V1.96 V (0.28%)41.1 W✓ OK (≤3%)
35 mm²125 A97 A0.85 V (0.12%)689.2 V1.4 V (0.2%)29.3 W✓ OK (≤3%)
50 mm²151 A118 A0.59 V (0.09%)689.4 V0.98 V (0.14%)20.5 W✓ OK (≤3%)
70 mm²192 A150 A0.42 V (0.06%)689.6 V0.7 V (0.1%)14.7 W✓ OK (≤3%)
95 mm²232 A181 A0.31 V (0.05%)689.7 V0.51 V (0.07%)10.8 W✓ OK (≤3%)
120 mm²269 A210 A0.25 V (0.04%)689.8 V0.41 V (0.06%)8.6 W✓ OK (≤3%)
150 mm²309 A241 A0.2 V (0.03%)689.8 V0.33 V (0.05%)6.8 W✓ OK (≤3%)
185 mm²353 A275 A0.16 V (0.02%)689.8 V0.26 V (0.04%)5.6 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.02%)689.9 V0.2 V (0.03%)4.3 W✓ OK (≤3%)
300 mm²477 A372 A0.1 V (0.01%)689.9 V0.16 V (0.02%)3.4 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.01%)689.9 V0.12 V (0.02%)2.6 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 20A at 40 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 20A over 40m at 690V (voltage drop: 11.86V or 1.72%).

What is the power capacity of 20A at 690V?

At unity power factor, 20A at 690V supports 23.9 kW with a standard 20A circuit breaker.