200 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 10.81V (2.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.7V (2.58%)
Voltage at Load404.2 VLine Loss: 3745.0 W
Max Power & Breaker143.76 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1729.74 V (416.81%)0.0 V2853.27 V (687.53%)599200.0 WDrop High
2.5 mm²24 A18 A1037.84 V (250.08%)0.0 V1711.96 V (412.52%)359520.0 WDrop High
4 mm²32 A25 A648.65 V (156.3%)0.0 V1069.97 V (257.83%)224700.0 WDrop High
6 mm²41 A32 A432.44 V (104.2%)0.0 V713.32 V (171.88%)149800.0 WDrop High
10 mm²57 A44 A259.46 V (62.52%)155.5 V427.99 V (103.13%)89880.0 WDrop High
16 mm²76 A59 A162.16 V (39.08%)252.8 V267.49 V (64.46%)56175.0 WDrop High
25 mm²101 A78 A103.78 V (25.01%)311.2 V171.2 V (41.25%)35952.0 WDrop High
35 mm²125 A97 A74.13 V (17.86%)340.9 V122.28 V (29.47%)25680.0 WDrop High
50 mm²151 A118 A51.89 V (12.5%)363.1 V85.6 V (20.63%)17976.0 WDrop High
70 mm²192 A150 A37.07 V (8.93%)377.9 V61.14 V (14.73%)12840.0 WDrop High
95 mm²232 A181 A27.31 V (6.58%)387.7 V45.05 V (10.86%)9461.1 WDrop High
120 mm²269 A210 A21.62 V (5.21%)393.4 V35.67 V (8.59%)7490.0 WDrop High
150 mm²309 A241 A17.3 V (4.17%)397.7 V28.53 V (6.88%)5992.0 W~ ≤5%
185 mm²353 A275 A14.02 V (3.38%)401.0 V23.13 V (5.57%)4858.4 W~ ≤5%
240 mm²415 A324 A10.81 V (2.61%)404.2 V17.83 V (4.3%)3745.0 W✓ OK (≤3%)
300 mm²477 A372 A8.65 V (2.08%)406.4 V14.27 V (3.44%)2996.0 W✓ OK (≤3%)
400 mm²570 A445 A6.49 V (1.56%)408.5 V10.7 V (2.58%)2247.0 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 200A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 200A over 350m at 415V (voltage drop: 10.81V or 2.61%).

What is the power capacity of 200A at 415V?

At unity power factor, 200A at 415V supports 143.76 kW with a standard 200A circuit breaker.