80 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 350 m (1148.3 ft).
Copper Cable (≤3% Drop)95 mm²Drop: 10.92V (2.63%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 11.41V (2.75%)
Voltage at Load404.1 VLine Loss: 1513.8 W
Max Power & Breaker57.5 kW80A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 350m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 691.9 V (166.72%) | 0.0 V | 1141.31 V (275.01%) | 95872.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 415.14 V (100.03%) | 0.0 V | 684.78 V (165.01%) | 57523.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 259.46 V (62.52%) | 155.5 V | 427.99 V (103.13%) | 35952.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 172.97 V (41.68%) | 242.0 V | 285.33 V (68.75%) | 23968.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 103.78 V (25.01%) | 311.2 V | 171.2 V (41.25%) | 14380.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 64.87 V (15.63%) | 350.1 V | 107.0 V (25.78%) | 8988.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 41.51 V (10.0%) | 373.5 V | 68.48 V (16.5%) | 5752.3 W | Drop High |
| 35 mm² | 125 A | 97 A | 29.65 V (7.15%) | 385.3 V | 48.91 V (11.79%) | 4108.8 W | Drop High |
| 50 mm² | 151 A | 118 A | 20.76 V (5.0%) | 394.2 V | 34.24 V (8.25%) | 2876.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 14.83 V (3.57%) | 400.2 V | 24.46 V (5.89%) | 2054.4 W | ~ ≤5% |
| 95 mm² | 232 A | 181 A | 10.92 V (2.63%) | 404.1 V | 18.02 V (4.34%) | 1513.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 8.65 V (2.08%) | 406.4 V | 14.27 V (3.44%) | 1198.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 6.92 V (1.67%) | 408.1 V | 11.41 V (2.75%) | 958.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 5.61 V (1.35%) | 409.4 V | 9.25 V (2.23%) | 777.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 4.32 V (1.04%) | 410.7 V | 7.13 V (1.72%) | 599.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 3.46 V (0.83%) | 411.5 V | 5.71 V (1.38%) | 479.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 2.59 V (0.63%) | 412.4 V | 4.28 V (1.03%) | 359.5 W | ✓ OK (≤3%) |
FAQ — 80 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 80A at 350 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 80A over 350m at 415V (voltage drop: 10.92V or 2.63%).
What is the power capacity of 80A at 415V?
At unity power factor, 80A at 415V supports 57.5 kW with a standard 80A circuit breaker.
Related Lengths & Currents (415V)
80A · 5m (415V)80A · 10m (415V)80A · 15m (415V)80A · 20m (415V)80A · 25m (415V)80A · 30m (415V)80A · 35m (415V)80A · 40m (415V)80A · 45m (415V)80A · 50m (415V)80A · 60m (415V)80A · 70m (415V)10A · 350m (415V)16A · 350m (415V)20A · 350m (415V)25A · 350m (415V)32A · 350m (415V)40A · 350m (415V)50A · 350m (415V)63A · 350m (415V)100A · 350m (415V)125A · 350m (415V)160A · 350m (415V)200A · 350m (415V)