⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 10.7V (2.58%)
Voltage at Load405.7 VLine Loss: 401.2 W
Max Power & Breaker17.97 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A216.22 V (52.1%)198.8 V356.66 V (85.94%)9362.5 WDrop High
2.5 mm²24 A18 A129.73 V (31.26%)285.3 V213.99 V (51.57%)5617.5 WDrop High
4 mm²32 A25 A81.08 V (19.54%)333.9 V133.75 V (32.23%)3510.9 WDrop High
6 mm²41 A32 A54.05 V (13.03%)360.9 V89.16 V (21.49%)2340.6 WDrop High
10 mm²57 A44 A32.43 V (7.82%)382.6 V53.5 V (12.89%)1404.4 WDrop High
16 mm²76 A59 A20.27 V (4.88%)394.7 V33.44 V (8.06%)877.7 W~ ≤5%
25 mm²101 A78 A12.97 V (3.13%)402.0 V21.4 V (5.16%)561.8 W~ ≤5%
35 mm²125 A97 A9.27 V (2.23%)405.7 V15.29 V (3.68%)401.2 W✓ OK (≤3%)
50 mm²151 A118 A6.49 V (1.56%)408.5 V10.7 V (2.58%)280.9 W✓ OK (≤3%)
70 mm²192 A150 A4.63 V (1.12%)410.4 V7.64 V (1.84%)200.6 W✓ OK (≤3%)
95 mm²232 A181 A3.41 V (0.82%)411.6 V5.63 V (1.36%)147.8 W✓ OK (≤3%)
120 mm²269 A210 A2.7 V (0.65%)412.3 V4.46 V (1.07%)117.0 W✓ OK (≤3%)
150 mm²309 A241 A2.16 V (0.52%)412.8 V3.57 V (0.86%)93.6 W✓ OK (≤3%)
185 mm²353 A275 A1.75 V (0.42%)413.2 V2.89 V (0.7%)75.9 W✓ OK (≤3%)
240 mm²415 A324 A1.35 V (0.33%)413.6 V2.23 V (0.54%)58.5 W✓ OK (≤3%)
300 mm²477 A372 A1.08 V (0.26%)413.9 V1.78 V (0.43%)46.8 W✓ OK (≤3%)
400 mm²570 A445 A0.81 V (0.2%)414.2 V1.34 V (0.32%)35.1 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 25A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 25A over 350m at 415V (voltage drop: 9.27V or 2.23%).

What is the power capacity of 25A at 415V?

At unity power factor, 25A at 415V supports 17.97 kW with a standard 25A circuit breaker.