10 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 350 m (1148.3 ft).
Copper Cable (≤3% Drop)16 mm²Drop: 8.11V (1.95%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 8.56V (2.06%)
Voltage at Load406.9 VLine Loss: 140.4 W
Max Power & Breaker7.19 kW10A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 350m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 86.49 V (20.84%) | 328.5 V | 142.66 V (34.38%) | 1498.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 51.89 V (12.5%) | 363.1 V | 85.6 V (20.63%) | 898.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 32.43 V (7.82%) | 382.6 V | 53.5 V (12.89%) | 561.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 21.62 V (5.21%) | 393.4 V | 35.67 V (8.59%) | 374.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 12.97 V (3.13%) | 402.0 V | 21.4 V (5.16%) | 224.7 W | ~ ≤5% |
| 16 mm² | 76 A | 59 A | 8.11 V (1.95%) | 406.9 V | 13.37 V (3.22%) | 140.4 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 5.19 V (1.25%) | 409.8 V | 8.56 V (2.06%) | 89.9 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 3.71 V (0.89%) | 411.3 V | 6.11 V (1.47%) | 64.2 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 2.59 V (0.63%) | 412.4 V | 4.28 V (1.03%) | 44.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.85 V (0.45%) | 413.1 V | 3.06 V (0.74%) | 32.1 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.37 V (0.33%) | 413.6 V | 2.25 V (0.54%) | 23.7 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.08 V (0.26%) | 413.9 V | 1.78 V (0.43%) | 18.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.86 V (0.21%) | 414.1 V | 1.43 V (0.34%) | 15.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.7 V (0.17%) | 414.3 V | 1.16 V (0.28%) | 12.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.54 V (0.13%) | 414.5 V | 0.89 V (0.21%) | 9.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.43 V (0.1%) | 414.6 V | 0.71 V (0.17%) | 7.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.32 V (0.08%) | 414.7 V | 0.53 V (0.13%) | 5.6 W | ✓ OK (≤3%) |
FAQ — 10 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 10A at 350 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 10A over 350m at 415V (voltage drop: 8.11V or 1.95%).
What is the power capacity of 10A at 415V?
At unity power factor, 10A at 415V supports 7.19 kW with a standard 10A circuit breaker.
Related Lengths & Currents (415V)
10A · 5m (415V)10A · 10m (415V)10A · 15m (415V)10A · 20m (415V)10A · 25m (415V)10A · 30m (415V)10A · 35m (415V)10A · 40m (415V)10A · 45m (415V)10A · 50m (415V)10A · 60m (415V)10A · 70m (415V)16A · 350m (415V)20A · 350m (415V)25A · 350m (415V)32A · 350m (415V)40A · 350m (415V)50A · 350m (415V)63A · 350m (415V)80A · 350m (415V)100A · 350m (415V)125A · 350m (415V)160A · 350m (415V)200A · 350m (415V)