200 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 200 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 19.77V (2.86%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 20.38V (2.95%)
Voltage at Load670.2 VLine Loss: 6848.0 W
Max Power & Breaker239.02 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1976.85 V (286.5%)0.0 V3260.87 V (472.59%)684800.0 WDrop High
2.5 mm²24 A18 A1186.11 V (171.9%)0.0 V1956.52 V (283.55%)410880.0 WDrop High
4 mm²32 A25 A741.32 V (107.44%)0.0 V1222.83 V (177.22%)256800.0 WDrop High
6 mm²41 A32 A494.21 V (71.62%)195.8 V815.22 V (118.15%)171200.0 WDrop High
10 mm²57 A44 A296.53 V (42.97%)393.5 V489.13 V (70.89%)102720.0 WDrop High
16 mm²76 A59 A185.33 V (26.86%)504.7 V305.71 V (44.31%)64200.0 WDrop High
25 mm²101 A78 A118.61 V (17.19%)571.4 V195.65 V (28.36%)41088.0 WDrop High
35 mm²125 A97 A84.72 V (12.28%)605.3 V139.75 V (20.25%)29348.6 WDrop High
50 mm²151 A118 A59.31 V (8.59%)630.7 V97.83 V (14.18%)20544.0 WDrop High
70 mm²192 A150 A42.36 V (6.14%)647.6 V69.88 V (10.13%)14674.3 WDrop High
95 mm²232 A181 A31.21 V (4.52%)658.8 V51.49 V (7.46%)10812.6 W~ ≤5%
120 mm²269 A210 A24.71 V (3.58%)665.3 V40.76 V (5.91%)8560.0 W~ ≤5%
150 mm²309 A241 A19.77 V (2.86%)670.2 V32.61 V (4.73%)6848.0 W✓ OK (≤3%)
185 mm²353 A275 A16.03 V (2.32%)674.0 V26.44 V (3.83%)5552.4 W✓ OK (≤3%)
240 mm²415 A324 A12.36 V (1.79%)677.6 V20.38 V (2.95%)4280.0 W✓ OK (≤3%)
300 mm²477 A372 A9.88 V (1.43%)680.1 V16.3 V (2.36%)3424.0 W✓ OK (≤3%)
400 mm²570 A445 A7.41 V (1.07%)682.6 V12.23 V (1.77%)2568.0 W✓ OK (≤3%)

FAQ — 200 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 200A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 200A over 400m at 690V (voltage drop: 19.77V or 2.86%).

What is the power capacity of 200A at 690V?

At unity power factor, 200A at 690V supports 239.02 kW with a standard 200A circuit breaker.