⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

20 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 20 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 18.53V (2.69%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 19.57V (2.84%)
Voltage at Load671.5 VLine Loss: 642.0 W
Max Power & Breaker23.9 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A197.68 V (28.65%)492.3 V326.09 V (47.26%)6848.0 WDrop High
2.5 mm²24 A18 A118.61 V (17.19%)571.4 V195.65 V (28.36%)4108.8 WDrop High
4 mm²32 A25 A74.13 V (10.74%)615.9 V122.28 V (17.72%)2568.0 WDrop High
6 mm²41 A32 A49.42 V (7.16%)640.6 V81.52 V (11.81%)1712.0 WDrop High
10 mm²57 A44 A29.65 V (4.3%)660.3 V48.91 V (7.09%)1027.2 W~ ≤5%
16 mm²76 A59 A18.53 V (2.69%)671.5 V30.57 V (4.43%)642.0 W✓ OK (≤3%)
25 mm²101 A78 A11.86 V (1.72%)678.1 V19.57 V (2.84%)410.9 W✓ OK (≤3%)
35 mm²125 A97 A8.47 V (1.23%)681.5 V13.98 V (2.03%)293.5 W✓ OK (≤3%)
50 mm²151 A118 A5.93 V (0.86%)684.1 V9.78 V (1.42%)205.4 W✓ OK (≤3%)
70 mm²192 A150 A4.24 V (0.61%)685.8 V6.99 V (1.01%)146.7 W✓ OK (≤3%)
95 mm²232 A181 A3.12 V (0.45%)686.9 V5.15 V (0.75%)108.1 W✓ OK (≤3%)
120 mm²269 A210 A2.47 V (0.36%)687.5 V4.08 V (0.59%)85.6 W✓ OK (≤3%)
150 mm²309 A241 A1.98 V (0.29%)688.0 V3.26 V (0.47%)68.5 W✓ OK (≤3%)
185 mm²353 A275 A1.6 V (0.23%)688.4 V2.64 V (0.38%)55.5 W✓ OK (≤3%)
240 mm²415 A324 A1.24 V (0.18%)688.8 V2.04 V (0.3%)42.8 W✓ OK (≤3%)
300 mm²477 A372 A0.99 V (0.14%)689.0 V1.63 V (0.24%)34.2 W✓ OK (≤3%)
400 mm²570 A445 A0.74 V (0.11%)689.3 V1.22 V (0.18%)25.7 W✓ OK (≤3%)

FAQ — 20 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 20A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 20A over 400m at 690V (voltage drop: 18.53V or 2.69%).

What is the power capacity of 20A at 690V?

At unity power factor, 20A at 690V supports 23.9 kW with a standard 20A circuit breaker.