10 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 10 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 14.83V (2.15%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 15.29V (2.22%)
Voltage at Load675.2 VLine Loss: 256.8 W
Max Power & Breaker11.95 kW10A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A98.84 V (14.32%)591.2 V163.04 V (23.63%)1712.0 WDrop High
2.5 mm²24 A18 A59.31 V (8.59%)630.7 V97.83 V (14.18%)1027.2 WDrop High
4 mm²32 A25 A37.07 V (5.37%)652.9 V61.14 V (8.86%)642.0 WDrop High
6 mm²41 A32 A24.71 V (3.58%)665.3 V40.76 V (5.91%)428.0 W~ ≤5%
10 mm²57 A44 A14.83 V (2.15%)675.2 V24.46 V (3.54%)256.8 W✓ OK (≤3%)
16 mm²76 A59 A9.27 V (1.34%)680.7 V15.29 V (2.22%)160.5 W✓ OK (≤3%)
25 mm²101 A78 A5.93 V (0.86%)684.1 V9.78 V (1.42%)102.7 W✓ OK (≤3%)
35 mm²125 A97 A4.24 V (0.61%)685.8 V6.99 V (1.01%)73.4 W✓ OK (≤3%)
50 mm²151 A118 A2.97 V (0.43%)687.0 V4.89 V (0.71%)51.4 W✓ OK (≤3%)
70 mm²192 A150 A2.12 V (0.31%)687.9 V3.49 V (0.51%)36.7 W✓ OK (≤3%)
95 mm²232 A181 A1.56 V (0.23%)688.4 V2.57 V (0.37%)27.0 W✓ OK (≤3%)
120 mm²269 A210 A1.24 V (0.18%)688.8 V2.04 V (0.3%)21.4 W✓ OK (≤3%)
150 mm²309 A241 A0.99 V (0.14%)689.0 V1.63 V (0.24%)17.1 W✓ OK (≤3%)
185 mm²353 A275 A0.8 V (0.12%)689.2 V1.32 V (0.19%)13.9 W✓ OK (≤3%)
240 mm²415 A324 A0.62 V (0.09%)689.4 V1.02 V (0.15%)10.7 W✓ OK (≤3%)
300 mm²477 A372 A0.49 V (0.07%)689.5 V0.82 V (0.12%)8.6 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.05%)689.6 V0.61 V (0.09%)6.4 W✓ OK (≤3%)

FAQ — 10 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 10A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 10A over 400m at 690V (voltage drop: 14.83V or 2.15%).

What is the power capacity of 10A at 690V?

At unity power factor, 10A at 690V supports 11.95 kW with a standard 10A circuit breaker.