32 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 18.98V (2.75%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 15.65V (2.27%)
Voltage at Load671.0 VLine Loss: 1051.9 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A316.3 V (45.84%)373.7 V521.74 V (75.61%)17530.9 WDrop High
2.5 mm²24 A18 A189.78 V (27.5%)500.2 V313.04 V (45.37%)10518.5 WDrop High
4 mm²32 A25 A118.61 V (17.19%)571.4 V195.65 V (28.36%)6574.1 WDrop High
6 mm²41 A32 A79.07 V (11.46%)610.9 V130.43 V (18.9%)4382.7 WDrop High
10 mm²57 A44 A47.44 V (6.88%)642.6 V78.26 V (11.34%)2629.6 WDrop High
16 mm²76 A59 A29.65 V (4.3%)660.3 V48.91 V (7.09%)1643.5 W~ ≤5%
25 mm²101 A78 A18.98 V (2.75%)671.0 V31.3 V (4.54%)1051.9 W✓ OK (≤3%)
35 mm²125 A97 A13.56 V (1.96%)676.4 V22.36 V (3.24%)751.3 W✓ OK (≤3%)
50 mm²151 A118 A9.49 V (1.38%)680.5 V15.65 V (2.27%)525.9 W✓ OK (≤3%)
70 mm²192 A150 A6.78 V (0.98%)683.2 V11.18 V (1.62%)375.7 W✓ OK (≤3%)
95 mm²232 A181 A4.99 V (0.72%)685.0 V8.24 V (1.19%)276.8 W✓ OK (≤3%)
120 mm²269 A210 A3.95 V (0.57%)686.0 V6.52 V (0.95%)219.1 W✓ OK (≤3%)
150 mm²309 A241 A3.16 V (0.46%)686.8 V5.22 V (0.76%)175.3 W✓ OK (≤3%)
185 mm²353 A275 A2.56 V (0.37%)687.4 V4.23 V (0.61%)142.1 W✓ OK (≤3%)
240 mm²415 A324 A1.98 V (0.29%)688.0 V3.26 V (0.47%)109.6 W✓ OK (≤3%)
300 mm²477 A372 A1.58 V (0.23%)688.4 V2.61 V (0.38%)87.7 W✓ OK (≤3%)
400 mm²570 A445 A1.19 V (0.17%)688.8 V1.96 V (0.28%)65.7 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 32A over 400m at 690V (voltage drop: 18.98V or 2.75%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.