80 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 16.94V (2.46%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 20.59V (2.98%)
Voltage at Load673.1 VLine Loss: 2347.9 W
Max Power & Breaker95.61 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A790.74 V (114.6%)0.0 V1304.35 V (189.04%)109568.0 WDrop High
2.5 mm²24 A18 A474.44 V (68.76%)215.6 V782.61 V (113.42%)65740.8 WDrop High
4 mm²32 A25 A296.53 V (42.97%)393.5 V489.13 V (70.89%)41088.0 WDrop High
6 mm²41 A32 A197.68 V (28.65%)492.3 V326.09 V (47.26%)27392.0 WDrop High
10 mm²57 A44 A118.61 V (17.19%)571.4 V195.65 V (28.36%)16435.2 WDrop High
16 mm²76 A59 A74.13 V (10.74%)615.9 V122.28 V (17.72%)10272.0 WDrop High
25 mm²101 A78 A47.44 V (6.88%)642.6 V78.26 V (11.34%)6574.1 WDrop High
35 mm²125 A97 A33.89 V (4.91%)656.1 V55.9 V (8.1%)4695.8 W~ ≤5%
50 mm²151 A118 A23.72 V (3.44%)666.3 V39.13 V (5.67%)3287.0 W~ ≤5%
70 mm²192 A150 A16.94 V (2.46%)673.1 V27.95 V (4.05%)2347.9 W✓ OK (≤3%)
95 mm²232 A181 A12.49 V (1.81%)677.5 V20.59 V (2.98%)1730.0 W✓ OK (≤3%)
120 mm²269 A210 A9.88 V (1.43%)680.1 V16.3 V (2.36%)1369.6 W✓ OK (≤3%)
150 mm²309 A241 A7.91 V (1.15%)682.1 V13.04 V (1.89%)1095.7 W✓ OK (≤3%)
185 mm²353 A275 A6.41 V (0.93%)683.6 V10.58 V (1.53%)888.4 W✓ OK (≤3%)
240 mm²415 A324 A4.94 V (0.72%)685.1 V8.15 V (1.18%)684.8 W✓ OK (≤3%)
300 mm²477 A372 A3.95 V (0.57%)686.0 V6.52 V (0.95%)547.8 W✓ OK (≤3%)
400 mm²570 A445 A2.97 V (0.43%)687.0 V4.89 V (0.71%)410.9 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 400 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 80A at 400 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 80A over 400m at 690V (voltage drop: 16.94V or 2.46%).

What is the power capacity of 80A at 690V?

At unity power factor, 80A at 690V supports 95.61 kW with a standard 80A circuit breaker.