⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

225 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 10.53V (1.53%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 11.01V (1.59%)
Voltage at Load679.5 VLine Loss: 4105.4 W
Max Power & Breaker268.9 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A667.19 V (96.69%)22.8 V1100.55 V (159.5%)260010.0 WDrop High
2.5 mm²24 A18 A400.31 V (58.02%)289.7 V660.33 V (95.7%)156006.0 WDrop High
4 mm²32 A25 A250.19 V (36.26%)439.8 V412.7 V (59.81%)97503.8 WDrop High
6 mm²41 A32 A166.8 V (24.17%)523.2 V275.14 V (39.87%)65002.5 WDrop High
10 mm²57 A44 A100.08 V (14.5%)589.9 V165.08 V (23.92%)39001.5 WDrop High
16 mm²76 A59 A62.55 V (9.07%)627.5 V103.18 V (14.95%)24375.9 WDrop High
25 mm²101 A78 A40.03 V (5.8%)650.0 V66.03 V (9.57%)15600.6 WDrop High
35 mm²125 A97 A28.59 V (4.14%)661.4 V47.17 V (6.84%)11143.3 WDrop High
50 mm²151 A118 A20.02 V (2.9%)670.0 V33.02 V (4.78%)7800.3 WDrop High
70 mm²192 A150 A14.3 V (2.07%)675.7 V23.58 V (3.42%)5571.6 WDrop High
95 mm²232 A181 A10.53 V (1.53%)679.5 V17.38 V (2.52%)4105.4 W✓ OK (≤3%)
120 mm²269 A210 A8.34 V (1.21%)681.7 V13.76 V (1.99%)3250.1 W✓ OK (≤3%)
150 mm²309 A241 A6.67 V (0.97%)683.3 V11.01 V (1.59%)2600.1 W✓ OK (≤3%)
185 mm²353 A275 A5.41 V (0.78%)684.6 V8.92 V (1.29%)2108.2 W✓ OK (≤3%)
240 mm²415 A324 A4.17 V (0.6%)685.8 V6.88 V (1.0%)1625.1 W✓ OK (≤3%)
300 mm²477 A372 A3.34 V (0.48%)686.7 V5.5 V (0.8%)1300.0 W✓ OK (≤3%)
400 mm²570 A445 A2.5 V (0.36%)687.5 V4.13 V (0.6%)975.0 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 225A at 120 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 225A over 120m at 690V (voltage drop: 10.53V or 1.53%).

What is the power capacity of 225A at 690V?

At unity power factor, 225A at 690V supports 268.9 kW with a standard 225A circuit breaker.