225 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 13.17V (1.91%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 13.76V (1.99%)
Voltage at Load676.8 VLine Loss: 5131.8 W
Max Power & Breaker268.9 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A833.98 V (120.87%)0.0 V1375.68 V (199.37%)325012.5 WDrop High
2.5 mm²24 A18 A500.39 V (72.52%)189.6 V825.41 V (119.62%)195007.5 WDrop High
4 mm²32 A25 A312.74 V (45.33%)377.3 V515.88 V (74.77%)121879.7 WDrop High
6 mm²41 A32 A208.5 V (30.22%)481.5 V343.92 V (49.84%)81253.1 WDrop High
10 mm²57 A44 A125.1 V (18.13%)564.9 V206.35 V (29.91%)48751.9 WDrop High
16 mm²76 A59 A78.19 V (11.33%)611.8 V128.97 V (18.69%)30469.9 WDrop High
25 mm²101 A78 A50.04 V (7.25%)640.0 V82.54 V (11.96%)19500.7 WDrop High
35 mm²125 A97 A35.74 V (5.18%)654.3 V58.96 V (8.54%)13929.1 WDrop High
50 mm²151 A118 A25.02 V (3.63%)665.0 V41.27 V (5.98%)9750.4 WDrop High
70 mm²192 A150 A17.87 V (2.59%)672.1 V29.48 V (4.27%)6964.6 WDrop High
95 mm²232 A181 A13.17 V (1.91%)676.8 V21.72 V (3.15%)5131.8 W✓ OK (≤3%)
120 mm²269 A210 A10.42 V (1.51%)679.6 V17.2 V (2.49%)4062.7 W✓ OK (≤3%)
150 mm²309 A241 A8.34 V (1.21%)681.7 V13.76 V (1.99%)3250.1 W✓ OK (≤3%)
185 mm²353 A275 A6.76 V (0.98%)683.2 V11.15 V (1.62%)2635.2 W✓ OK (≤3%)
240 mm²415 A324 A5.21 V (0.76%)684.8 V8.6 V (1.25%)2031.3 W✓ OK (≤3%)
300 mm²477 A372 A4.17 V (0.6%)685.8 V6.88 V (1.0%)1625.1 W✓ OK (≤3%)
400 mm²570 A445 A3.13 V (0.45%)686.9 V5.16 V (0.75%)1218.8 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 150 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 225A at 150 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 225A over 150m at 690V (voltage drop: 13.17V or 1.91%).

What is the power capacity of 225A at 690V?

At unity power factor, 225A at 690V supports 268.9 kW with a standard 225A circuit breaker.