⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 15.44V (2.24%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 15.29V (2.22%)
Voltage at Load674.6 VLine Loss: 668.7 W
Max Power & Breaker29.88 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A61.78 V (8.95%)628.2 V101.9 V (14.77%)2675.0 WDrop High
2.5 mm²24 A18 A37.07 V (5.37%)652.9 V61.14 V (8.86%)1605.0 WDrop High
4 mm²32 A25 A23.17 V (3.36%)666.8 V38.21 V (5.54%)1003.1 W~ ≤5%
6 mm²41 A32 A15.44 V (2.24%)674.6 V25.48 V (3.69%)668.7 W✓ OK (≤3%)
10 mm²57 A44 A9.27 V (1.34%)680.7 V15.29 V (2.22%)401.2 W✓ OK (≤3%)
16 mm²76 A59 A5.79 V (0.84%)684.2 V9.55 V (1.38%)250.8 W✓ OK (≤3%)
25 mm²101 A78 A3.71 V (0.54%)686.3 V6.11 V (0.89%)160.5 W✓ OK (≤3%)
35 mm²125 A97 A2.65 V (0.38%)687.4 V4.37 V (0.63%)114.6 W✓ OK (≤3%)
50 mm²151 A118 A1.85 V (0.27%)688.1 V3.06 V (0.44%)80.2 W✓ OK (≤3%)
70 mm²192 A150 A1.32 V (0.19%)688.7 V2.18 V (0.32%)57.3 W✓ OK (≤3%)
95 mm²232 A181 A0.98 V (0.14%)689.0 V1.61 V (0.23%)42.2 W✓ OK (≤3%)
120 mm²269 A210 A0.77 V (0.11%)689.2 V1.27 V (0.18%)33.4 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.09%)689.4 V1.02 V (0.15%)26.7 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.07%)689.5 V0.83 V (0.12%)21.7 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.06%)689.6 V0.64 V (0.09%)16.7 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.04%)689.7 V0.51 V (0.07%)13.4 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.03%)689.8 V0.38 V (0.06%)10.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 25A at 100 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 25A over 100m at 690V (voltage drop: 15.44V or 2.24%).

What is the power capacity of 25A at 690V?

At unity power factor, 25A at 690V supports 29.88 kW with a standard 25A circuit breaker.