32 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 19.77V (2.86%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 19.57V (2.84%)
Voltage at Load670.2 VLine Loss: 1095.7 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A79.07 V (11.46%)610.9 V130.43 V (18.9%)4382.7 WDrop High
2.5 mm²24 A18 A47.44 V (6.88%)642.6 V78.26 V (11.34%)2629.6 WDrop High
4 mm²32 A25 A29.65 V (4.3%)660.3 V48.91 V (7.09%)1643.5 W~ ≤5%
6 mm²41 A32 A19.77 V (2.86%)670.2 V32.61 V (4.73%)1095.7 W✓ OK (≤3%)
10 mm²57 A44 A11.86 V (1.72%)678.1 V19.57 V (2.84%)657.4 W✓ OK (≤3%)
16 mm²76 A59 A7.41 V (1.07%)682.6 V12.23 V (1.77%)410.9 W✓ OK (≤3%)
25 mm²101 A78 A4.74 V (0.69%)685.3 V7.83 V (1.13%)263.0 W✓ OK (≤3%)
35 mm²125 A97 A3.39 V (0.49%)686.6 V5.59 V (0.81%)187.8 W✓ OK (≤3%)
50 mm²151 A118 A2.37 V (0.34%)687.6 V3.91 V (0.57%)131.5 W✓ OK (≤3%)
70 mm²192 A150 A1.69 V (0.25%)688.3 V2.8 V (0.41%)93.9 W✓ OK (≤3%)
95 mm²232 A181 A1.25 V (0.18%)688.8 V2.06 V (0.3%)69.2 W✓ OK (≤3%)
120 mm²269 A210 A0.99 V (0.14%)689.0 V1.63 V (0.24%)54.8 W✓ OK (≤3%)
150 mm²309 A241 A0.79 V (0.11%)689.2 V1.3 V (0.19%)43.8 W✓ OK (≤3%)
185 mm²353 A275 A0.64 V (0.09%)689.4 V1.06 V (0.15%)35.5 W✓ OK (≤3%)
240 mm²415 A324 A0.49 V (0.07%)689.5 V0.82 V (0.12%)27.4 W✓ OK (≤3%)
300 mm²477 A372 A0.4 V (0.06%)689.6 V0.65 V (0.09%)21.9 W✓ OK (≤3%)
400 mm²570 A445 A0.3 V (0.04%)689.7 V0.49 V (0.07%)16.4 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 100 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 32A over 100m at 690V (voltage drop: 19.77V or 2.86%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.