⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 200 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 1.43V (2.97%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.18V (2.45%)
Voltage at Load46.6 VLine Loss: 35.7 W
Max Power & Breaker1.2 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A142.67 V (297.22%)0.0 V235.33 V (490.28%)3566.7 WDrop High
2.5 mm²24 A18 A85.6 V (178.33%)0.0 V141.2 V (294.17%)2140.0 WDrop High
4 mm²32 A25 A53.5 V (111.46%)0.0 V88.25 V (183.85%)1337.5 WDrop High
6 mm²41 A32 A35.67 V (74.31%)12.3 V58.83 V (122.57%)891.7 WDrop High
10 mm²57 A44 A21.4 V (44.58%)26.6 V35.3 V (73.54%)535.0 WDrop High
16 mm²76 A59 A13.37 V (27.86%)34.6 V22.06 V (45.96%)334.4 WDrop High
25 mm²101 A78 A8.56 V (17.83%)39.4 V14.12 V (29.42%)214.0 WDrop High
35 mm²125 A97 A6.11 V (12.74%)41.9 V10.09 V (21.01%)152.9 WDrop High
50 mm²151 A118 A4.28 V (8.92%)43.7 V7.06 V (14.71%)107.0 WDrop High
70 mm²192 A150 A3.06 V (6.37%)44.9 V5.04 V (10.51%)76.4 WDrop High
95 mm²232 A181 A2.25 V (4.69%)45.7 V3.72 V (7.74%)56.3 W~ ≤5%
120 mm²269 A210 A1.78 V (3.72%)46.2 V2.94 V (6.13%)44.6 W~ ≤5%
150 mm²309 A241 A1.43 V (2.97%)46.6 V2.35 V (4.9%)35.7 W✓ OK (≤3%)
185 mm²353 A275 A1.16 V (2.41%)46.8 V1.91 V (3.98%)28.9 W✓ OK (≤3%)
240 mm²415 A324 A0.89 V (1.86%)47.1 V1.47 V (3.06%)22.3 W✓ OK (≤3%)
300 mm²477 A372 A0.71 V (1.49%)47.3 V1.18 V (2.45%)17.8 W✓ OK (≤3%)
400 mm²570 A445 A0.53 V (1.11%)47.5 V0.88 V (1.84%)13.4 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 200 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 25A at 200 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 25A over 200m at 48V (voltage drop: 1.43V or 2.97%).

What is the power capacity of 25A at 48V?

At unity power factor, 25A at 48V supports 1.2 kW with a standard 25A circuit breaker.