25 Amp Cable Size at 50 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 0.56V (2.35%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 0.59V (2.45%)
Voltage at Load23.4 VLine Loss: 14.1 W
Max Power & Breaker0.6 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A35.67 V (148.61%)0.0 V58.83 V (245.14%)891.7 WDrop High
2.5 mm²24 A18 A21.4 V (89.17%)2.6 V35.3 V (147.08%)535.0 WDrop High
4 mm²32 A25 A13.37 V (55.73%)10.6 V22.06 V (91.93%)334.4 WDrop High
6 mm²41 A32 A8.92 V (37.15%)15.1 V14.71 V (61.28%)222.9 WDrop High
10 mm²57 A44 A5.35 V (22.29%)18.6 V8.82 V (36.77%)133.7 WDrop High
16 mm²76 A59 A3.34 V (13.93%)20.7 V5.52 V (22.98%)83.6 WDrop High
25 mm²101 A78 A2.14 V (8.92%)21.9 V3.53 V (14.71%)53.5 WDrop High
35 mm²125 A97 A1.53 V (6.37%)22.5 V2.52 V (10.51%)38.2 WDrop High
50 mm²151 A118 A1.07 V (4.46%)22.9 V1.76 V (7.35%)26.7 W~ ≤5%
70 mm²192 A150 A0.76 V (3.18%)23.2 V1.26 V (5.25%)19.1 W~ ≤5%
95 mm²232 A181 A0.56 V (2.35%)23.4 V0.93 V (3.87%)14.1 W✓ OK (≤3%)
120 mm²269 A210 A0.45 V (1.86%)23.6 V0.74 V (3.06%)11.1 W✓ OK (≤3%)
150 mm²309 A241 A0.36 V (1.49%)23.6 V0.59 V (2.45%)8.9 W✓ OK (≤3%)
185 mm²353 A275 A0.29 V (1.2%)23.7 V0.48 V (1.99%)7.2 W✓ OK (≤3%)
240 mm²415 A324 A0.22 V (0.93%)23.8 V0.37 V (1.53%)5.6 W✓ OK (≤3%)
300 mm²477 A372 A0.18 V (0.74%)23.8 V0.29 V (1.23%)4.5 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.56%)23.9 V0.22 V (0.92%)3.3 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 50 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 25A at 50 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 25A over 50m at 24V (voltage drop: 0.56V or 2.35%).

What is the power capacity of 25A at 24V?

At unity power factor, 25A at 24V supports 0.6 kW with a standard 25A circuit breaker.