250 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 0.77V (0.11%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 0.83V (0.12%)
Voltage at Load689.2 VLine Loss: 334.4 W
Max Power & Breaker298.78 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A61.78 V (8.95%)628.2 V101.9 V (14.77%)26750.0 WDrop High
2.5 mm²24 A18 A37.07 V (5.37%)652.9 V61.14 V (8.86%)16050.0 WDrop High
4 mm²32 A25 A23.17 V (3.36%)666.8 V38.21 V (5.54%)10031.2 WDrop High
6 mm²41 A32 A15.44 V (2.24%)674.6 V25.48 V (3.69%)6687.5 WDrop High
10 mm²57 A44 A9.27 V (1.34%)680.7 V15.29 V (2.22%)4012.5 WDrop High
16 mm²76 A59 A5.79 V (0.84%)684.2 V9.55 V (1.38%)2507.8 WDrop High
25 mm²101 A78 A3.71 V (0.54%)686.3 V6.11 V (0.89%)1605.0 WDrop High
35 mm²125 A97 A2.65 V (0.38%)687.4 V4.37 V (0.63%)1146.4 WDrop High
50 mm²151 A118 A1.85 V (0.27%)688.1 V3.06 V (0.44%)802.5 WDrop High
70 mm²192 A150 A1.32 V (0.19%)688.7 V2.18 V (0.32%)573.2 WDrop High
95 mm²232 A181 A0.98 V (0.14%)689.0 V1.61 V (0.23%)422.4 WDrop High
120 mm²269 A210 A0.77 V (0.11%)689.2 V1.27 V (0.18%)334.4 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.09%)689.4 V1.02 V (0.15%)267.5 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.07%)689.5 V0.83 V (0.12%)216.9 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.06%)689.6 V0.64 V (0.09%)167.2 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.04%)689.7 V0.51 V (0.07%)133.8 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.03%)689.8 V0.38 V (0.06%)100.3 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 10 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 250A at 10 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 250A over 10m at 690V (voltage drop: 0.77V or 0.11%).

What is the power capacity of 250A at 690V?

At unity power factor, 250A at 690V supports 298.78 kW with a standard 250A circuit breaker.