⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

250 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 1.93V (0.28%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 2.07V (0.3%)
Voltage at Load688.1 VLine Loss: 835.9 W
Max Power & Breaker298.78 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A154.44 V (22.38%)535.6 V254.76 V (36.92%)66875.0 WDrop High
2.5 mm²24 A18 A92.66 V (13.43%)597.3 V152.85 V (22.15%)40125.0 WDrop High
4 mm²32 A25 A57.92 V (8.39%)632.1 V95.53 V (13.85%)25078.1 WDrop High
6 mm²41 A32 A38.61 V (5.6%)651.4 V63.69 V (9.23%)16718.8 WDrop High
10 mm²57 A44 A23.17 V (3.36%)666.8 V38.21 V (5.54%)10031.2 WDrop High
16 mm²76 A59 A14.48 V (2.1%)675.5 V23.88 V (3.46%)6269.5 WDrop High
25 mm²101 A78 A9.27 V (1.34%)680.7 V15.29 V (2.22%)4012.5 WDrop High
35 mm²125 A97 A6.62 V (0.96%)683.4 V10.92 V (1.58%)2866.1 WDrop High
50 mm²151 A118 A4.63 V (0.67%)685.4 V7.64 V (1.11%)2006.2 WDrop High
70 mm²192 A150 A3.31 V (0.48%)686.7 V5.46 V (0.79%)1433.0 WDrop High
95 mm²232 A181 A2.44 V (0.35%)687.6 V4.02 V (0.58%)1055.9 WDrop High
120 mm²269 A210 A1.93 V (0.28%)688.1 V3.18 V (0.46%)835.9 W✓ OK (≤3%)
150 mm²309 A241 A1.54 V (0.22%)688.5 V2.55 V (0.37%)668.7 W✓ OK (≤3%)
185 mm²353 A275 A1.25 V (0.18%)688.7 V2.07 V (0.3%)542.2 W✓ OK (≤3%)
240 mm²415 A324 A0.97 V (0.14%)689.0 V1.59 V (0.23%)418.0 W✓ OK (≤3%)
300 mm²477 A372 A0.77 V (0.11%)689.2 V1.27 V (0.18%)334.4 W✓ OK (≤3%)
400 mm²570 A445 A0.58 V (0.08%)689.4 V0.96 V (0.14%)250.8 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 250A at 25 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 250A over 25m at 690V (voltage drop: 1.93V or 0.28%).

What is the power capacity of 250A at 690V?

At unity power factor, 250A at 690V supports 298.78 kW with a standard 250A circuit breaker.