⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

250 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 250 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 1.16V (0.17%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 1.24V (0.18%)
Voltage at Load688.8 VLine Loss: 501.6 W
Max Power & Breaker298.78 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A92.66 V (13.43%)597.3 V152.85 V (22.15%)40125.0 WDrop High
2.5 mm²24 A18 A55.6 V (8.06%)634.4 V91.71 V (13.29%)24075.0 WDrop High
4 mm²32 A25 A34.75 V (5.04%)655.3 V57.32 V (8.31%)15046.9 WDrop High
6 mm²41 A32 A23.17 V (3.36%)666.8 V38.21 V (5.54%)10031.2 WDrop High
10 mm²57 A44 A13.9 V (2.01%)676.1 V22.93 V (3.32%)6018.8 WDrop High
16 mm²76 A59 A8.69 V (1.26%)681.3 V14.33 V (2.08%)3761.7 WDrop High
25 mm²101 A78 A5.56 V (0.81%)684.4 V9.17 V (1.33%)2407.5 WDrop High
35 mm²125 A97 A3.97 V (0.58%)686.0 V6.55 V (0.95%)1719.6 WDrop High
50 mm²151 A118 A2.78 V (0.4%)687.2 V4.59 V (0.66%)1203.8 WDrop High
70 mm²192 A150 A1.99 V (0.29%)688.0 V3.28 V (0.47%)859.8 WDrop High
95 mm²232 A181 A1.46 V (0.21%)688.5 V2.41 V (0.35%)633.6 WDrop High
120 mm²269 A210 A1.16 V (0.17%)688.8 V1.91 V (0.28%)501.6 W✓ OK (≤3%)
150 mm²309 A241 A0.93 V (0.13%)689.1 V1.53 V (0.22%)401.2 W✓ OK (≤3%)
185 mm²353 A275 A0.75 V (0.11%)689.2 V1.24 V (0.18%)325.3 W✓ OK (≤3%)
240 mm²415 A324 A0.58 V (0.08%)689.4 V0.96 V (0.14%)250.8 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (0.07%)689.5 V0.76 V (0.11%)200.6 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (0.05%)689.7 V0.57 V (0.08%)150.5 W✓ OK (≤3%)

FAQ — 250 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 250A at 15 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 250A over 15m at 690V (voltage drop: 1.16V or 0.17%).

What is the power capacity of 250A at 690V?

At unity power factor, 250A at 690V supports 298.78 kW with a standard 250A circuit breaker.