30 Amp Cable Size at 30 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 0.55V (2.29%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 0.67V (2.79%)
Voltage at Load23.4 VLine Loss: 16.5 W
Max Power & Breaker0.72 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A25.68 V (107.0%)0.0 V42.36 V (176.5%)770.4 WDrop High
2.5 mm²24 A18 A15.41 V (64.2%)8.6 V25.42 V (105.9%)462.2 WDrop High
4 mm²32 A25 A9.63 V (40.13%)14.4 V15.88 V (66.19%)288.9 WDrop High
6 mm²41 A32 A6.42 V (26.75%)17.6 V10.59 V (44.12%)192.6 WDrop High
10 mm²57 A44 A3.85 V (16.05%)20.1 V6.35 V (26.47%)115.6 WDrop High
16 mm²76 A59 A2.41 V (10.03%)21.6 V3.97 V (16.55%)72.2 WDrop High
25 mm²101 A78 A1.54 V (6.42%)22.5 V2.54 V (10.59%)46.2 WDrop High
35 mm²125 A97 A1.1 V (4.59%)22.9 V1.82 V (7.56%)33.0 W~ ≤5%
50 mm²151 A118 A0.77 V (3.21%)23.2 V1.27 V (5.29%)23.1 W~ ≤5%
70 mm²192 A150 A0.55 V (2.29%)23.4 V0.91 V (3.78%)16.5 W✓ OK (≤3%)
95 mm²232 A181 A0.41 V (1.69%)23.6 V0.67 V (2.79%)12.2 W✓ OK (≤3%)
120 mm²269 A210 A0.32 V (1.34%)23.7 V0.53 V (2.21%)9.6 W✓ OK (≤3%)
150 mm²309 A241 A0.26 V (1.07%)23.7 V0.42 V (1.76%)7.7 W✓ OK (≤3%)
185 mm²353 A275 A0.21 V (0.87%)23.8 V0.34 V (1.43%)6.2 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.67%)23.8 V0.26 V (1.1%)4.8 W✓ OK (≤3%)
300 mm²477 A372 A0.13 V (0.53%)23.9 V0.21 V (0.88%)3.9 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.4%)23.9 V0.16 V (0.66%)2.9 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 30 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 30A at 30 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 30A over 30m at 24V (voltage drop: 0.55V or 2.29%).

What is the power capacity of 30A at 24V?

At unity power factor, 30A at 24V supports 0.72 kW with a standard 30A circuit breaker.