30 Amp Cable Size at 50 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)95 mm²Drop: 0.68V (2.82%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 0.71V (2.94%)
Voltage at Load23.3 VLine Loss: 20.3 W
Max Power & Breaker0.72 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A42.8 V (178.33%)0.0 V70.6 V (294.17%)1284.0 WDrop High
2.5 mm²24 A18 A25.68 V (107.0%)0.0 V42.36 V (176.5%)770.4 WDrop High
4 mm²32 A25 A16.05 V (66.87%)8.0 V26.47 V (110.31%)481.5 WDrop High
6 mm²41 A32 A10.7 V (44.58%)13.3 V17.65 V (73.54%)321.0 WDrop High
10 mm²57 A44 A6.42 V (26.75%)17.6 V10.59 V (44.12%)192.6 WDrop High
16 mm²76 A59 A4.01 V (16.72%)20.0 V6.62 V (27.58%)120.4 WDrop High
25 mm²101 A78 A2.57 V (10.7%)21.4 V4.24 V (17.65%)77.0 WDrop High
35 mm²125 A97 A1.83 V (7.64%)22.2 V3.03 V (12.61%)55.0 WDrop High
50 mm²151 A118 A1.28 V (5.35%)22.7 V2.12 V (8.82%)38.5 WDrop High
70 mm²192 A150 A0.92 V (3.82%)23.1 V1.51 V (6.3%)27.5 W~ ≤5%
95 mm²232 A181 A0.68 V (2.82%)23.3 V1.11 V (4.64%)20.3 W✓ OK (≤3%)
120 mm²269 A210 A0.53 V (2.23%)23.5 V0.88 V (3.68%)16.0 W✓ OK (≤3%)
150 mm²309 A241 A0.43 V (1.78%)23.6 V0.71 V (2.94%)12.8 W✓ OK (≤3%)
185 mm²353 A275 A0.35 V (1.45%)23.7 V0.57 V (2.39%)10.4 W✓ OK (≤3%)
240 mm²415 A324 A0.27 V (1.11%)23.7 V0.44 V (1.84%)8.0 W✓ OK (≤3%)
300 mm²477 A372 A0.21 V (0.89%)23.8 V0.35 V (1.47%)6.4 W✓ OK (≤3%)
400 mm²570 A445 A0.16 V (0.67%)23.8 V0.26 V (1.1%)4.8 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 50 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 30A at 50 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 30A over 50m at 24V (voltage drop: 0.68V or 2.82%).

What is the power capacity of 30A at 24V?

At unity power factor, 30A at 24V supports 0.72 kW with a standard 30A circuit breaker.