30 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 0.64V (2.67%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 0.66V (2.76%)
Voltage at Load23.4 VLine Loss: 19.3 W
Max Power & Breaker0.72 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4.28 V (17.83%)19.7 V7.06 V (29.42%)128.4 WDrop High
2.5 mm²24 A18 A2.57 V (10.7%)21.4 V4.24 V (17.65%)77.0 WDrop High
4 mm²32 A25 A1.6 V (6.69%)22.4 V2.65 V (11.03%)48.1 WDrop High
6 mm²41 A32 A1.07 V (4.46%)22.9 V1.76 V (7.35%)32.1 W~ ≤5%
10 mm²57 A44 A0.64 V (2.67%)23.4 V1.06 V (4.41%)19.3 W✓ OK (≤3%)
16 mm²76 A59 A0.4 V (1.67%)23.6 V0.66 V (2.76%)12.0 W✓ OK (≤3%)
25 mm²101 A78 A0.26 V (1.07%)23.7 V0.42 V (1.76%)7.7 W✓ OK (≤3%)
35 mm²125 A97 A0.18 V (0.76%)23.8 V0.3 V (1.26%)5.5 W✓ OK (≤3%)
50 mm²151 A118 A0.13 V (0.53%)23.9 V0.21 V (0.88%)3.9 W✓ OK (≤3%)
70 mm²192 A150 A0.09 V (0.38%)23.9 V0.15 V (0.63%)2.8 W✓ OK (≤3%)
95 mm²232 A181 A0.07 V (0.28%)23.9 V0.11 V (0.46%)2.0 W✓ OK (≤3%)
120 mm²269 A210 A0.05 V (0.22%)23.9 V0.09 V (0.37%)1.6 W✓ OK (≤3%)
150 mm²309 A241 A0.04 V (0.18%)24.0 V0.07 V (0.29%)1.3 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.14%)24.0 V0.06 V (0.24%)1.0 W✓ OK (≤3%)
240 mm²415 A324 A0.03 V (0.11%)24.0 V0.04 V (0.18%)0.8 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.09%)24.0 V0.04 V (0.15%)0.6 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.07%)24.0 V0.03 V (0.11%)0.5 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 30A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 30A over 5m at 24V (voltage drop: 0.64V or 2.67%).

What is the power capacity of 30A at 24V?

At unity power factor, 30A at 24V supports 0.72 kW with a standard 30A circuit breaker.