30 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 0.64V (2.67%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 0.56V (2.32%)
Voltage at Load23.4 VLine Loss: 19.3 W
Max Power & Breaker0.72 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A21.4 V (89.17%)2.6 V35.3 V (147.08%)642.0 WDrop High
2.5 mm²24 A18 A12.84 V (53.5%)11.2 V21.18 V (88.25%)385.2 WDrop High
4 mm²32 A25 A8.02 V (33.44%)16.0 V13.24 V (55.16%)240.7 WDrop High
6 mm²41 A32 A5.35 V (22.29%)18.6 V8.82 V (36.77%)160.5 WDrop High
10 mm²57 A44 A3.21 V (13.37%)20.8 V5.29 V (22.06%)96.3 WDrop High
16 mm²76 A59 A2.01 V (8.36%)22.0 V3.31 V (13.79%)60.2 WDrop High
25 mm²101 A78 A1.28 V (5.35%)22.7 V2.12 V (8.82%)38.5 WDrop High
35 mm²125 A97 A0.92 V (3.82%)23.1 V1.51 V (6.3%)27.5 W~ ≤5%
50 mm²151 A118 A0.64 V (2.67%)23.4 V1.06 V (4.41%)19.3 W✓ OK (≤3%)
70 mm²192 A150 A0.46 V (1.91%)23.5 V0.76 V (3.15%)13.8 W✓ OK (≤3%)
95 mm²232 A181 A0.34 V (1.41%)23.7 V0.56 V (2.32%)10.1 W✓ OK (≤3%)
120 mm²269 A210 A0.27 V (1.11%)23.7 V0.44 V (1.84%)8.0 W✓ OK (≤3%)
150 mm²309 A241 A0.21 V (0.89%)23.8 V0.35 V (1.47%)6.4 W✓ OK (≤3%)
185 mm²353 A275 A0.17 V (0.72%)23.8 V0.29 V (1.19%)5.2 W✓ OK (≤3%)
240 mm²415 A324 A0.13 V (0.56%)23.9 V0.22 V (0.92%)4.0 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.45%)23.9 V0.18 V (0.74%)3.2 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.33%)23.9 V0.13 V (0.55%)2.4 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 25 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 30A at 25 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 30A over 25m at 24V (voltage drop: 0.64V or 2.67%).

What is the power capacity of 30A at 24V?

At unity power factor, 30A at 24V supports 0.72 kW with a standard 30A circuit breaker.