30 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 0.51V (2.14%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 0.61V (2.52%)
Voltage at Load23.5 VLine Loss: 15.4 W
Max Power & Breaker0.72 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8.56 V (35.67%)15.4 V14.12 V (58.83%)256.8 WDrop High
2.5 mm²24 A18 A5.14 V (21.4%)18.9 V8.47 V (35.3%)154.1 WDrop High
4 mm²32 A25 A3.21 V (13.38%)20.8 V5.29 V (22.06%)96.3 WDrop High
6 mm²41 A32 A2.14 V (8.92%)21.9 V3.53 V (14.71%)64.2 WDrop High
10 mm²57 A44 A1.28 V (5.35%)22.7 V2.12 V (8.82%)38.5 WDrop High
16 mm²76 A59 A0.8 V (3.34%)23.2 V1.32 V (5.52%)24.1 W~ ≤5%
25 mm²101 A78 A0.51 V (2.14%)23.5 V0.85 V (3.53%)15.4 W✓ OK (≤3%)
35 mm²125 A97 A0.37 V (1.53%)23.6 V0.61 V (2.52%)11.0 W✓ OK (≤3%)
50 mm²151 A118 A0.26 V (1.07%)23.7 V0.42 V (1.76%)7.7 W✓ OK (≤3%)
70 mm²192 A150 A0.18 V (0.76%)23.8 V0.3 V (1.26%)5.5 W✓ OK (≤3%)
95 mm²232 A181 A0.14 V (0.56%)23.9 V0.22 V (0.93%)4.1 W✓ OK (≤3%)
120 mm²269 A210 A0.11 V (0.45%)23.9 V0.18 V (0.74%)3.2 W✓ OK (≤3%)
150 mm²309 A241 A0.09 V (0.36%)23.9 V0.14 V (0.59%)2.6 W✓ OK (≤3%)
185 mm²353 A275 A0.07 V (0.29%)23.9 V0.11 V (0.48%)2.1 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.22%)23.9 V0.09 V (0.37%)1.6 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.18%)24.0 V0.07 V (0.29%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.13%)24.0 V0.05 V (0.22%)1.0 W✓ OK (≤3%)

FAQ — 30 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 30A at 10 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 30A over 10m at 24V (voltage drop: 0.51V or 2.14%).

What is the power capacity of 30A at 24V?

At unity power factor, 30A at 24V supports 0.72 kW with a standard 30A circuit breaker.