300 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 500 m (1640.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.95V (1.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.93V (5.52%)
Voltage at Load408.1 VLine Loss: 3611.2 W
Max Power & Breaker215.64 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3706.59 V (893.15%)0.0 V6114.14 V (1473.29%)1926000.0 WDrop High
2.5 mm²24 A18 A2223.95 V (535.89%)0.0 V3668.48 V (883.97%)1155600.0 WDrop High
4 mm²32 A25 A1389.97 V (334.93%)0.0 V2292.8 V (552.48%)722250.0 WDrop High
6 mm²41 A32 A926.65 V (223.29%)0.0 V1528.53 V (368.32%)481500.0 WDrop High
10 mm²57 A44 A555.99 V (133.97%)0.0 V917.12 V (220.99%)288900.0 WDrop High
16 mm²76 A59 A347.49 V (83.73%)67.5 V573.2 V (138.12%)180562.5 WDrop High
25 mm²101 A78 A222.4 V (53.59%)192.6 V366.85 V (88.4%)115560.0 WDrop High
35 mm²125 A97 A158.85 V (38.28%)256.1 V262.03 V (63.14%)82542.9 WDrop High
50 mm²151 A118 A111.2 V (26.79%)303.8 V183.42 V (44.2%)57780.0 WDrop High
70 mm²192 A150 A79.43 V (19.14%)335.6 V131.02 V (31.57%)41271.4 WDrop High
95 mm²232 A181 A58.53 V (14.1%)356.5 V96.54 V (23.26%)30410.5 WDrop High
120 mm²269 A210 A46.33 V (11.16%)368.7 V76.43 V (18.42%)24075.0 WDrop High
150 mm²309 A241 A37.07 V (8.93%)377.9 V61.14 V (14.73%)19260.0 WDrop High
185 mm²353 A275 A30.05 V (7.24%)384.9 V49.57 V (11.95%)15616.2 WDrop High
240 mm²415 A324 A23.17 V (5.58%)391.8 V38.21 V (9.21%)12037.5 WDrop High
300 mm²477 A372 A18.53 V (4.47%)396.5 V30.57 V (7.37%)9630.0 W~ ≤5%
400 mm²570 A445 A13.9 V (3.35%)401.1 V22.93 V (5.52%)7222.5 W~ ≤5%

FAQ — 300 Amp Cable Size at 500 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 300A at 500 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 300A over 500m at 415V (voltage drop: 6.95V or 1.68%).

What is the power capacity of 300A at 415V?

At unity power factor, 300A at 415V supports 215.64 kW with a standard 300A circuit breaker.