325 Amp Cable Size at 250 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 10.04V (2.51%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.42V (3.1%)
Voltage at Load390.0 VLine Loss: 5650.9 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2007.74 V (501.93%)0.0 V3311.83 V (827.96%)1130187.5 WDrop High
2.5 mm²24 A18 A1204.64 V (301.16%)0.0 V1987.1 V (496.77%)678112.5 WDrop High
4 mm²32 A25 A752.9 V (188.23%)0.0 V1241.93 V (310.48%)423820.3 WDrop High
6 mm²41 A32 A501.93 V (125.48%)0.0 V827.96 V (206.99%)282546.9 WDrop High
10 mm²57 A44 A301.16 V (75.29%)98.8 V496.77 V (124.19%)169528.1 WDrop High
16 mm²76 A59 A188.23 V (47.06%)211.8 V310.48 V (77.62%)105955.1 WDrop High
25 mm²101 A78 A120.46 V (30.12%)279.5 V198.71 V (49.68%)67811.2 WDrop High
35 mm²125 A97 A86.05 V (21.51%)314.0 V141.94 V (35.48%)48436.6 WDrop High
50 mm²151 A118 A60.23 V (15.06%)339.8 V99.35 V (24.84%)33905.6 WDrop High
70 mm²192 A150 A43.02 V (10.76%)357.0 V70.97 V (17.74%)24218.3 WDrop High
95 mm²232 A181 A31.7 V (7.93%)368.3 V52.29 V (13.07%)17845.1 WDrop High
120 mm²269 A210 A25.1 V (6.27%)374.9 V41.4 V (10.35%)14127.3 WDrop High
150 mm²309 A241 A20.08 V (5.02%)379.9 V33.12 V (8.28%)11301.9 WDrop High
185 mm²353 A275 A16.28 V (4.07%)383.7 V26.85 V (6.71%)9163.7 W~ ≤5%
240 mm²415 A324 A12.55 V (3.14%)387.5 V20.7 V (5.17%)7063.7 W~ ≤5%
300 mm²477 A372 A10.04 V (2.51%)390.0 V16.56 V (4.14%)5650.9 W✓ OK (≤3%)
400 mm²570 A445 A7.53 V (1.88%)392.5 V12.42 V (3.1%)4238.2 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 250 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 325A at 250 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 325A over 250m at 400V (voltage drop: 10.04V or 2.51%).

What is the power capacity of 325A at 400V?

At unity power factor, 325A at 400V supports 225.17 kW with a standard 350A circuit breaker.