325 Amp Cable Size at 30 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 30 m (98.4 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.39V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.72V (3.59%)
Voltage at Load46.6 VLine Loss: 452.1 W
Max Power & Breaker15.6 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A278.2 V (579.58%)0.0 V458.9 V (956.04%)90415.0 WDrop High
2.5 mm²24 A18 A166.92 V (347.75%)0.0 V275.34 V (573.62%)54249.0 WDrop High
4 mm²32 A25 A104.33 V (217.34%)0.0 V172.09 V (358.52%)33905.6 WDrop High
6 mm²41 A32 A69.55 V (144.9%)0.0 V114.72 V (239.01%)22603.8 WDrop High
10 mm²57 A44 A41.73 V (86.94%)6.3 V68.83 V (143.41%)13562.3 WDrop High
16 mm²76 A59 A26.08 V (54.34%)21.9 V43.02 V (89.63%)8476.4 WDrop High
25 mm²101 A78 A16.69 V (34.77%)31.3 V27.53 V (57.36%)5424.9 WDrop High
35 mm²125 A97 A11.92 V (24.84%)36.1 V19.67 V (40.97%)3874.9 WDrop High
50 mm²151 A118 A8.35 V (17.39%)39.7 V13.77 V (28.68%)2712.5 WDrop High
70 mm²192 A150 A5.96 V (12.42%)42.0 V9.83 V (20.49%)1937.5 WDrop High
95 mm²232 A181 A4.39 V (9.15%)43.6 V7.25 V (15.1%)1427.6 WDrop High
120 mm²269 A210 A3.48 V (7.24%)44.5 V5.74 V (11.95%)1130.2 WDrop High
150 mm²309 A241 A2.78 V (5.8%)45.2 V4.59 V (9.56%)904.1 WDrop High
185 mm²353 A275 A2.26 V (4.7%)45.7 V3.72 V (7.75%)733.1 W~ ≤5%
240 mm²415 A324 A1.74 V (3.62%)46.3 V2.87 V (5.98%)565.1 W~ ≤5%
300 mm²477 A372 A1.39 V (2.9%)46.6 V2.29 V (4.78%)452.1 W✓ OK (≤3%)
400 mm²570 A445 A1.04 V (2.17%)47.0 V1.72 V (3.59%)339.1 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 30 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 325A at 30 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 325A over 30m at 48V (voltage drop: 1.39V or 2.9%).

What is the power capacity of 325A at 48V?

At unity power factor, 325A at 48V supports 15.6 kW with a standard 350A circuit breaker.