⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 1.13V (2.35%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.15V (2.39%)
Voltage at Load46.9 VLine Loss: 366.5 W
Max Power & Breaker15.6 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A139.1 V (289.79%)0.0 V229.45 V (478.02%)45207.5 WDrop High
2.5 mm²24 A18 A83.46 V (173.88%)0.0 V137.67 V (286.81%)27124.5 WDrop High
4 mm²32 A25 A52.16 V (108.67%)0.0 V86.04 V (179.26%)16952.8 WDrop High
6 mm²41 A32 A34.77 V (72.45%)13.2 V57.36 V (119.51%)11301.9 WDrop High
10 mm²57 A44 A20.87 V (43.47%)27.1 V34.42 V (71.7%)6781.1 WDrop High
16 mm²76 A59 A13.04 V (27.17%)35.0 V21.51 V (44.81%)4238.2 WDrop High
25 mm²101 A78 A8.35 V (17.39%)39.7 V13.77 V (28.68%)2712.5 WDrop High
35 mm²125 A97 A5.96 V (12.42%)42.0 V9.83 V (20.49%)1937.5 WDrop High
50 mm²151 A118 A4.17 V (8.69%)43.8 V6.88 V (14.34%)1356.2 WDrop High
70 mm²192 A150 A2.98 V (6.21%)45.0 V4.92 V (10.24%)968.7 WDrop High
95 mm²232 A181 A2.2 V (4.58%)45.8 V3.62 V (7.55%)713.8 WDrop High
120 mm²269 A210 A1.74 V (3.62%)46.3 V2.87 V (5.98%)565.1 WDrop High
150 mm²309 A241 A1.39 V (2.9%)46.6 V2.29 V (4.78%)452.1 WDrop High
185 mm²353 A275 A1.13 V (2.35%)46.9 V1.86 V (3.88%)366.5 W✓ OK (≤3%)
240 mm²415 A324 A0.87 V (1.81%)47.1 V1.43 V (2.99%)282.5 W✓ OK (≤3%)
300 mm²477 A372 A0.7 V (1.45%)47.3 V1.15 V (2.39%)226.0 W✓ OK (≤3%)
400 mm²570 A445 A0.52 V (1.09%)47.5 V0.86 V (1.79%)169.5 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 325A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 15m at 48V (voltage drop: 1.13V or 2.35%).

What is the power capacity of 325A at 48V?

At unity power factor, 325A at 48V supports 15.6 kW with a standard 350A circuit breaker.