⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 0.75V (1.57%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 0.76V (1.59%)
Voltage at Load47.2 VLine Loss: 244.4 W
Max Power & Breaker15.6 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A92.73 V (193.19%)0.0 V152.97 V (318.68%)30138.3 WDrop High
2.5 mm²24 A18 A55.64 V (115.92%)0.0 V91.78 V (191.21%)18083.0 WDrop High
4 mm²32 A25 A34.77 V (72.45%)13.2 V57.36 V (119.51%)11301.9 WDrop High
6 mm²41 A32 A23.18 V (48.3%)24.8 V38.24 V (79.67%)7534.6 WDrop High
10 mm²57 A44 A13.91 V (28.98%)34.1 V22.95 V (47.8%)4520.8 WDrop High
16 mm²76 A59 A8.69 V (18.11%)39.3 V14.34 V (29.88%)2825.5 WDrop High
25 mm²101 A78 A5.56 V (11.59%)42.4 V9.18 V (19.12%)1808.3 WDrop High
35 mm²125 A97 A3.97 V (8.28%)44.0 V6.56 V (13.66%)1291.6 WDrop High
50 mm²151 A118 A2.78 V (5.8%)45.2 V4.59 V (9.56%)904.1 WDrop High
70 mm²192 A150 A1.99 V (4.14%)46.0 V3.28 V (6.83%)645.8 WDrop High
95 mm²232 A181 A1.46 V (3.05%)46.5 V2.42 V (5.03%)475.9 WDrop High
120 mm²269 A210 A1.16 V (2.41%)46.8 V1.91 V (3.98%)376.7 WDrop High
150 mm²309 A241 A0.93 V (1.93%)47.1 V1.53 V (3.19%)301.4 WDrop High
185 mm²353 A275 A0.75 V (1.57%)47.2 V1.24 V (2.58%)244.4 W✓ OK (≤3%)
240 mm²415 A324 A0.58 V (1.21%)47.4 V0.96 V (1.99%)188.4 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (0.97%)47.5 V0.76 V (1.59%)150.7 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (0.72%)47.7 V0.57 V (1.2%)113.0 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 10 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 325A at 10 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 10m at 48V (voltage drop: 0.75V or 1.57%).

What is the power capacity of 325A at 48V?